• It is important to choose the proper size for AC cable.
• Strip off all wires for 24 mm.
• The cross-sectional area for each internal cable is 2~2/0 AWG.
Figure 3-13 : Stripping cables for M88H
_122
AC terminal
N
PE
L1
L2
L3
outer
jacket
Stripping length: 24 ~26mm
Conductor cross-section:
2~2/0 AWG (35 ~ 70mm²)
Please follow the following steps for assembling the AC terminal (M88H
_122
) :
3.3.2 Required Protective Devices and AC Cabling
Installation for M88H
_122
It is recommended to install an upstream circuit breaker between AC side and
inverter side for over current protection.
Model
Upstream circuit breaker
M88H
≧
150A
Sizes of Cables (mm)
D1
D2
D3
D4
43.5
∼
51.3
34.8
∼
43.5
27.2
∼
34.8
23.9
∼
27.2
8.5
∼
11
8.5
∼
11
8.5
∼
11
8.5
∼
11
1
∼
4
1
∼
5
1
∼
3.5
1
∼
3.5
Torque (N
•
m)
Dimension of P (mm)
Figure 3-14: AC Gland with multiple inlet (M88H
_122
)
Table 3-2: Cable size comparison table (M88H
_122
)
D1
D3
D2
D4
P
27
Installation
Summary of Contents for M88 Series
Page 2: ......
Page 29: ...Figure 3 16 AC gland assembling for M88H_122 Torque 0 8 N m to fix the screw 29 Installation ...
Page 96: ......
Page 97: ...M88H 操作手冊 三相併網型變流器 The power behind competitiveness www deltaww com English 1 97 繁體中文 ...
Page 117: ...要使用遮蔽板 請參考圖3 9的安裝方式 鎖附扭力45 kgf cm 圖3 9 遮蔽板的安裝方法 117 安裝 ...
Page 124: ...圖3 16 M88H_122交流固定頭的組裝方式 Torque 0 8 N m to fix the screw 安裝 124 ...
Page 163: ...圖5 5 AC DC SPD 損壞時的告警 圖5 6 拔起連接線並移除螺絲 AC SPD DC SPD 163 維護 ...
Page 169: ...圖5 14 拆卸功率模組風扇 僅以單側為例 組裝所需的螺釘扭矩 8 kgf cm 0 8N m 169 維護 ...
Page 170: ...圖5 15 濾網拆卸方向 圖5 15為濾網位置 170 維護 ...
Page 174: ...7 卸下8顆螺絲並用手抓住功率模組使其與配線箱分開 8 確定密封蓋有蓋上 圖5 18 拆下8顆螺絲後 將配線箱與功率模組分離 174 維護 ...
Page 191: ......
Page 192: ...Version 04201204 ...