5 - 2 4
Modulon DPH Series
y
Use a voltage meter to measure whether the total voltage is around 12.5Vdc × the total
number of batteries after the batteries are connected in series.
y
The default battery quantity is 40 PCS of 12V batteries connected in series and you
should connect the external battery cabinet’s neutral (N) to the middle 20
th
and 21
st
batteries. You should use battery cables to connect the external battery cabinet to the
UPS’s Battery Input terminals '+', '-' and ‘N’. Please refer to
Figure 5-20
.
1
2
20
21
22
40
+ -
+ -
+ -
+ -
+
+
-
-
(
+
)
(
-
)
(N)
(
+
)
(
-
)
(N)
UPS’s Battery Input Terminals
Protective Device
External Battery
Cabinet
(Figure 5-20: External Battery Cabinet Connection)
WARNING:
A battery leak can short-circuit the batteries and lead to serious accidents. For
safety's sake, you must insulate the batteries from their touched metal cabinets
by installing insulated devices (e.g. insulated trays or boxes) in between. For
relevant information about the insulated materials for such application, please
contact Delta customer service.
y
Please follow your UPS rating to install an appropriate protective device for each exter-
nal battery cabinet. There are four installation methods for selection.
(1) A 4-pole DC circuit breaker or DC isolated switch connected in series with a DC fuse.
(2) A 3-pole DC circuit breaker or DC isolated switch connected in series with a DC fuse.
(3) A 4-pole DC circuit breaker.
(4) A 3-pole DC circuit breaker.
For relevant values, please refer to
Table 5-6
; for relevant installation diagrams, please
refer to
Figure 5-21
~
Figure 5-24
.
Summary of Contents for Modulon DPH series
Page 26: ......
Page 58: ......
Page 168: ......
Page 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 240: ......
Page 241: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 246: ......
Page 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 250: ......