6 - 3 9
6
UPS Operation
2
Tap the ON/ OFF Button (
) and the following screen will pop up to ask if you want
WRSRZHURႇWKH836¶VLQYHUWHU3OHDVHVHOHFW
YES
'.
ECO
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
10:15
May 25,2018
(Figure 6-53: Power off Reminder Screen)
3
After selection of '
YES
', the UPS will shut down the inverter, terminate each power
module’s output and let the bypass AC source supply power. If the bypass AC source
is abnormal, there is a risk of output interruption and the connected critical loads won’t
be protected. At this moment, each power module keeps charging the batteries, the tri-
color LED indicator illuminates yellow and the following screen appears (
Figure 6-54)
.
For the tri-color LED indicator location, please refer to
Figure 2-12
.
Bypass
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
(Figure 6-54: Bypass Mode Screen)
4
Please log in as an
Administrator
. For the
Administrator
password, please contact
service personnel. After login, ensure that you are in the
Administrator
login status
(see
Figure 6-55
).
Summary of Contents for Modulon DPH series
Page 26: ......
Page 58: ......
Page 168: ......
Page 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 240: ......
Page 241: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 246: ......
Page 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 250: ......