6 - 4 2
Modulon DPH Series
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
10:15
May 25,2018
Frequency
Conversion
(Figure 6-58: Power off Reminder Screen)
3
After selection of '
YES
', the UPS will shut down the inverter and terminate each power
module’s output. As there is no bypass output in Frequency Conversion mode, all
output will be terminated right after the inverter is shut down. Now, each power module
keeps charging the batteries, the tri-color LED indicator illuminates yellow and the
following screen appears (
Figure 6-59)
. For the tri-color LED indicator location, please
refer to
Figure 2-12
.
Standby
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Load
0 %
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
(Figure 6-59: Standby Mode Screen)
4
Switch
OFF
the Output Breaker (Q4) and log in as an
Administrator
. For the
Admini-
strator
password, please contact service personnel. After login, ensure that you are in
the
Administrator
login status (see
Figure 6-60
).
Summary of Contents for Modulon DPH series
Page 26: ......
Page 58: ......
Page 168: ......
Page 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 240: ......
Page 241: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 246: ......
Page 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 250: ......