5.3 External Battery Pack Connection
NOTE :
1. When connecting the external battery pack with the UPS, you must install
an appropriate non-fuse DC breaker or the fast-acting fuse that meets the
VDIHW\FHUWL¿FDWLRQ'RQRWXVHDQ$&EUHDNHU
2. The breaker must be a 2-pole non-fuse DC breaker with characteristics of
1-pole 250Vdc, 2-pole 500Vdc and 35kA (or above) DC breaking capacity.
z
For models UPS602N2004N035 (6 kVA ) & UPS103N2004N035 (10 kVA ):
1
Remove the two screws from the external battery connector’s panel shown
below.
)LJXUH5HPRYDORI([WHUQDO%DWWHU\&RQQHFWRU¶V3DQHO
(After Removal of External
Battery Connector’s Panel)
(Before Removal of External
Battery Connector’s Panel)
ON
OFF
EX T E R N A L B A T T . C O N N E C T O R
240Vdc.48A
SMART SLOT
RS-232
REPO
REPO
PARALLEL
PARALLEL
IN P U T
BR E A KE R
UPS O U T PU T
N
N
L
L
AC IN P U T
ON
OFF
EX TE R N A L B A TT . C O N N E C TO R
240Vdc.48A
SMART SLOT
RS-232
REPO
REPO
PARALLEL
PARALLEL
IN P U T
BR E A KE R
UPS O U T PU T
N
N
L
L
AC IN P U T
Two Screws
External Battery
Connector’s Panel