4 0
Amplon N Series
B. Cold Start
1
Please check the ‘+’ and ‘-’ poles and ensure that battery wring is correct.
2
Press and hold the
ON
button for 3 seconds and release it after you hear
one beep.
3
The UPS starts self-inspection. When the LCD shows
, it
means that the UPS is running in battery mode.
7.2 Turn-off
Procedures
1
Make sure that the connected loads have been completely turned off.
2
Press
and
hold
the
OFF
button for 3 seconds and release it after you hear one
beep.
3
Turn off the UPS’s input breaker.
4
Wait until the LCD backlight is completely off.
5
Turn off the external battery pack’s breaker.