Chapter 4 Installation & Wiring
30
Model
Wiring Location
Wire Gauge (*
1
)
Bolt Type Torque (Ib-in) (*
2
)
NT- 60K
Main Input
2 AWG X 1
M10
88.5
Reserve Input
4/0 AWG X1
M10
88.5
Output
4/0 AWG X1
M10
88.5
Battery
4/0 AWG X1
M8
130±4
PE
6 AWG X 1
M10
88.5
NT- 100K
Main Input
4/0 AWG X 1
M10
220±8
Reserve Input
2/0 AWG X 2
M10
220±8
Output
2/0 AWG X 2
M10
220±8
Battery
2/0 AWG X 2
M10
220±8
PE
3 AWG X 1
M10
220±8
z
External Terminal Selection:
For the external terminals that need to connect to the UPS, please refer to the
table below. The suggested manufacturer is K.S. TERMINALS INC. Other equiv-
DOHQWPDQXIDFWXUHUVRUWHUPLQDOVDUHDOVR¿QH
UPS Capacity (VA)
15K
30K
60K
100K
Main Input
RNB14-8
RNB14-8
RNBS38-10
SQNBS60-10
Reserve Input
RNB14-8
SQNBS22-8 SQNBS100-10 SQNBS80-10
Output
RNB14-8
SQNBS22-8 SQNBS100-10 SQNBS80-10
Battery
RNB14-8
SQNBS22-8
SQNBS100-8
SQNBS80-10