6.8.OTHER
This section contains DRM0, PARTIAL/ZERP EXPORT, DRY CONTACT
[
DRM0
]
[
PARTIAL/ZERO EXPORT
]
[
DRY CONTACT
]
[PARTIAL/ZERO EXPORT]
1. Click [On] to turn on the function.
2. Set the Sign capacity & PV capacity, DC1 will use the lower value as the power limit reference.
3. Set the Rate% base on power company or local regulation.
[DRY CONTACT]
1. Select the type of alert to trigger
2. When the Inverter triggers the selected alarm, DC1 will close dry contact relay to trigger external device.
[DRM0 (Digital input)]
1. Click [On] to turn on the function.
2. Follow below table to set the specific power limit value, you can check the percentage by DRM0(%) on the APP.
Inverter behavior (standard)
N/A
Power de-rating to 30%
Power de-rating to 0%
Power de-rating to 100%
Power de-rating to 60%
Short pins
16 & 15
16 & 14
16 & 13
16 & 12
16 & 11
Inverter behavior (AU)
Disconnect from grid
Power de-rating to 75%
Power de-rating to 100%
Power de-rating to 50%
Power de-rating to 0%
Short pins
16 & 15
16 & 14
16 & 13
16 & 12
16 & 11