24
Ultron HPH Integrated Battery Series
No.
Event
Description
14
Battery needs replace-
ment
Battery replacement date is due.
15
Bypass over temperature
warning/ shutdown
Bypass static switch temperature is too high.
16
Bypass static switch fail
The bypass static switch has open/ short issue.
17
Over temperature fail
When the UPS temperature is out of range.
18
General alarm
When any of above-mentioned events occurs.
7
Input Dry Contacts
The HPH UPS provides two sets of input dry contacts and they are normally open. The default set-
ting for Pin 1 & 2 is ‘ROO’ and the default setting for Pin 3 & 4 is ‘Generator Power Supply Signal’.
There are two types of configurations.
(Figure 5-5: Input Dry Contacts)
P1 P2
Pin 1
Pin 2
Pin 3
Pin 4
Figure 5-6
shows the 1
st
type of input dry contact configuration. It requires internal power, +12VSF.
UPS
6
4
1
3
6
4
1
3
GS
GS
+12VSF
1
2
3
4
2K(1206)
2K(1206)
2K(1206)
2K(1206)
(Figure 5-6: Input Dry Contact Configuration I)
Figure 5-7
shows the 2
nd
type of input dry contact configuration. It requires external power with a
voltage range between 6~12Vdc.