36
Ultron HPH Integrated Battery Series
2
Please ensure you understand the functions of the wiring terminal block shown in
Figure 6-8
.
No.
Item
Function
Description
1
AC Input
Terminal Block
Connects the main
AC source.
Includes three-phase (R, S, T) and
neutral (N) terminals.
2
For the UPS ground-
ing
Includes one grounding terminal.
3
UPS Output
Terminal Block
Connects the critical
loads.
Includes three-phase (R, S, T) and
neutral (N) terminals.
4
For the critical loads’
grounding
Includes one grounding terminal.
5
Battery Input
Terminal Block
Connects an external
battery cabinet.
Includes three terminals, positive
(+), negative (-) and neutral (N).
6
For an external bat-
tery cabinet’s ground-
ing
Includes one grounding terminal.
3
J '*%!|!|!_|
battery rating voltage is ±240Vdc.
4
J
OFF
position. For the posi-
tion of each breaker, please refer to
3.5 Rear Panel
.
5
According to the capacity and the model of your UPS, select proper input and output
cables (please refer to
Table 6-1
).
6
Connect the main AC source/ output/ external battery cabinet cables to the wiring ter-
minal block and do not forget to ground the UPS (please refer to
Figure 6-10~6-12
).
7
]+% >:'*>
No. GES203HH33B035 or GES303HH33B035 or GES403HH33B035, open the
UPS’s front door, install two strings of 40 batteries (not provided; for battery type,
please contact service personnel) and the battery kit (not provided; please refer to
Chapter 9: Optional Accessories
). For battery kit installation, please refer to
Figure
6-9
. Do not connect the batteries in reverse.
8
% ] + %
personnel can do this. After installation, make sure the battery fuse holders are open.
Please refer to
3.3 Front View with Door Open
for how to open/ close the internal
battery fuse holders.