Ultron HPH Series
103
Item
Description
System Redundancy
Set up how many UPSs that need to be preserved for
redundancy.
NOTE:
The system redundancy can be modified only when
the inverter is powered off, that is bypass mode or
standby mode.
Asnyc Transfer Time
When it is impossible for the inverter to reach synchronous
phase lock with the bypass, the output will be terminated
during conversion process according to this setup time.
Industrial Mode
Set up the industrial mode (disable or enable (default)).
Bypass Disable
Set up the bypass disable (disable (default) or enable).
System Sequential Start
Set up the time interval for the UPS to be converted from the
battery mode to online mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
7.9.4
Battery and Charging Setting
In the
Battery and Charging Setting
screen,
the administrator can set up the following items (as
shown in the figure below). These settings must be carried out by qualified service personnel, please
contact Delta service personnel for assistance.