creases volume, improves reliability and prolongs service life.
Wide AC input voltage range
(100% load: 176~276/ 305~478Vac; 70%~100% load: 132~276/ 228~478Vac) reduces
frequent transfer from normal mode to battery mode to save battery consumption and prolong
battery life.
Battery test in online mode and regular battery test prolong battery life.
Automatic input frequency detection enables operation at 50Hz or 60Hz.
You can parallel at maximum four UPS units for N+X parallel redundancy, capacity
expansion and reliability enhancement.
It is convenient to set the parameters and view operating conditions on the colorful touch
panel, so that management personnel can see them accurately and clearly.
It can set the output voltage on touch panel as: 220/ 230/ 240Vac.
The CPU can record up to 10000 entries of abnormal information of the UPS, which is
helpful in fault diagnosis for the UPS and in the improvement of the maintenance efficiency.
No-battery start-up: In case the external battery cabinet is not connected, the device can
still start up normally with normal main AC power.
REPO port: Under emergency status, use a user-supplied remote control switch to
disconnect the output immediately to prevent any danger.
Built-in RS232 port allows monitoring and management of the UPS via the UPSentry 2012
software (
https://datacenter-softwarecenter.deltaww.com.cn
).
Attaches optional accessories like Mini SNMP card for network communication.
Other optional accessories include Mini Relay I/O and Mini ModBus cards for dry contact,
and ModBus communication.
In order to improve the efficiency further, the UPS can be set to operate in ECO mode.
In case of any abnormal conditions, the UPS will transfer to online mode automatically.
Automatically detects and shows whether fans are operating normally.
The fans have automatic speed regulation function. With multi-stage control over the fan
speed, it can improve the reliability and the efficiency of the system, reduce the noise
and prolong the service life of the fans. What’s more, the UPS has the function of fan
failure detection
Provides equalized charge and float charge. You can adjust the charge current from 1A to
the maximum. Each adjustment level is 1A. The charging mode is set according to the actual
charging current so as to keep the batteries at full charging capacity and prolong the battery
life (float charge voltage: ±272Vdc; equalized charge voltage: ±280Vdc (This is only for lead
acid batteries)).