Ultron HPH Series
75
3. After selection of ‘
Power Off
’, the UPS will shut down the inverter and terminate the output.
As there is no bypass output in frequency conversion mode, all output will be terminated right
after the inverter is shut down. Now, the UPS keeps charging the batteries, the tri-color LED
indicator illuminates yellow and the following screen appears.
(Figure 6-39: Standby Mode Screen)
4. Switch
OFF
output breaker and log in as an
Administrator
. For the
Administrator
password,
please contact Delta service personnel. After login, ensure that you are in the
Administrator
login status.
5. Click
SETUP
→
Mode Setting
→
On-Line
. If the bypass voltage is in the normal range, the
UPS will run in bypass mode to let the bypass AC source supply power to the output.
(Figure 6-40: Select On-Line Mode)