77
2.
Press the ON/ OFF button ( ) once and the following screen will pop up to ask you if you
want to power off the UPS’s inverter. If yes, please select ‘
Power Off
’.
(Figure 6-42: Power Off Reminder Screen)
3.
After selection of ‘
Power Off
’, the UPS will stop aging test, and run in bypass mode. At this
moment, the tri-color LED indicator illuminates yellow and the following screen appears.
(Figure 6-43: Bypass Mode Screen)
4.
Switch
OFF
output breaker and log in as an
Administrator
. For the
Administrator
password,
please contact Delta service personnel. After login, ensure that you are in the
Administrator
login status.
5.
Click
SETUP
→
Mode Setting
→
On-Line
. If the bypass voltage is in the normal range, the