10
Amplon N Series
No.
Multi-
function
Button
Description
2
The button has multi-function. Please refer to the following for de-
tailed information.
1. Turn-off:
z
z
In on-line mode, press and hold the button for 3 seconds,
release it after you hear one beep and the inverter will be off
and the UPS will transfer to run in standby/ bypass mode.
The UPS will keep charging the batteries when the UPS is
in standby/ bypass mode even though the button has been
pressed. To fully turn off the UPS, it is advised to unplug the
input power cord.
z
z
In battery mode, press and hold the button for 3 seconds, re-
lease it after you hear one beep and the UPS will turn off its
output.
2. Fault clear:
When the UPS has a fault condition, press and hold the button
for 3 seconds, release it after you hear one beep and the UPS
will clear the fault condition and return to standby/ bypass mode.
Besides, the LCD will show the relevant error code. For error
code information, please refer to
3.3 LCD Display - No. 9
.
3. Scrolling down:
In setup mode, press the button for 0.1 second to go to the next
display.
3
The button has multi-function. Please refer to the following for de-
tailed information.
1. Scrolling down:
In non-setup mode, press the button for 0.1 second to go to the
next display.
2. Entering into the setup mode:
Press the button for 3 seconds and the UPS will enter into the
setup mode. For more information, please refer to
5.5 Setup
Mode
. Please note that only qualified service personnel can per
-
form setup action.
NOTE :
When the backlight of the LCD is off, you can press any button mentioned
above to wake up the display and enable each button function.