Chapter 9 Troubleshooting
29
B. About other problems that might happen:
No.
Problem
Possible Cause
Solution
1
Overload
The UPS is
overloaded.
Decrease your connected
loads.
2
Battery Missing
Internal battery cables
are not connected or
not firmly connected.
1. Contact service
personnel.
2. Connect the internal
battery cables and
connect them firmly.
3
Weak Battery/
Battery
Replacement
Batteries are
damaged or battery
life time is due.
Contact service personnel.
4
Abnormal Input
(when the AC icon
is flashing)
The AC input voltage
or frequency is out of
the acceptable bypass
range.
1. Check whether the
AC input voltage or
frequency is abnormal.
2. Contact service
personnel.
NOTE :
If all possible causes are eliminated but the alarm still appears, please
contact your local dealer or customer service.
Summary of Contents for UPS102N2000N0B0
Page 39: ......
Page 40: ...5013231700...