30
Amplon N Series
Chapter 10 : Maintenance
10.1 UPS
z
z
UPS Cleaning
Regularly clean the UPS, especially the slits and openings, to ensure that the
air freely flows into the UPS to avoid overheating. If necessary, use an air-gun
to clean the slits and openings to prevent any object from blocking or covering
these areas.
z
z
UPS Regular Inspection
Regularly check the UPS every half year and inspect:
1. Whether the UPS, LEDs, and alarm function are operating normally.
2. Whether battery voltage is normal. If battery voltage is too high or too low,
find the root cause.
10.2 Batteries
The N series UPS uses sealed lead-acid batteries. Though the typical battery life
cycle is 3~5 years, the battery life depends on the temperature, the usage, and the
charging/ discharging frequency. High temperature environments and high charging/
discharging frequency will quickly shorten the battery life. The UPS does not require
maintenance by the user; however, the batteries should be checked periodically.
Please follow the suggestions below to ensure a normal battery lifetime and
sufficient back-up time.
z
z
Keep the usage temperature at 20°C ~25°C.
z
z
Idle batteries must be fully recharged every three months if the UPS needs to be
stored for an extended period of time. Please fully charge the batteries (internal
and external) until the Battery Level Bar Graph shown on the UPS’s LCD is
fully on.
z
z
A loss of battery charge capacity may occur during shipping and storage. Before
1
st
use of the UPS, please fully charge the batteries (internal and external).
NOTE:
If the UPS’s internal batteries need to be replaced, please
contact qualified service personnel. During battery replacement, the
loads attached to the UPS will not be protected if input power fails.