32
Amplon N Series
Appendix 1 : Technical Specifications
Model
N-1K
N-2K
N-3K
Power
Rating
Standard Model
1kVA/0.9KW 2kVA/1.8KW 3kVA/2.7KW
Long Backup Model
1kVA/0.8KW 2kVA/1.6KW 3kVA/2.4KW
Waveform
Pure Sine Wave
Input
Nominal Voltage
220/230/240 Vac
Voltage Range
175 ~ 280 Vac (100% load);
80 ~ 175 Vac (50% ~ 100% load)
Frequency
50/60 Hz ± 10 Hz
Power Factor
> 0.99 (full load)
iTHD
< 3%
Output
Power Factor
0.9 (Standard Model)
0.8 (Long Backup Model)
Voltage
220/230/240 Vac
Voltage
Regulation
± 2% (linear load)
Frequency
50/60 Hz ± 0.05 Hz
vTHD
< 3% (linear load)
Overload
Capability
< 105%: continuous; 105% ~ 125%: 1 min
-
ute; 125% ~ 150%: 30 seconds
Cress Factor
3:1
Connection
India
socket x 3
India
socket x 4
India socket
x 3, Terminal
block x 1
Efficiency
Online Mode
91%
Up to 93%
Battery
Battery Voltage
24 Vdc
48 Vdc
72 Vdc