Delta UPS - Amplon Family 

R Series, Single Phase

1/ 2/ 3 kVA

Installation & Operation Quick Guide

ENGLISH

Product Introduction

1

1kVA

2/ 3kVA

ON

OFF

SETU

P

ON

OFF

SETU

P

The R series UPS, available in 1kVA, 2kVA and 3kVA, is a single-phase on-

line Uninterruptable Power Supply (UPS) system, which outputs reliable 

sine-wave power to your electrical equipment. The product is designed with 

advanced technology and high quality components. Its output power factor is 

up to 0.9 and efficiency in on-line mode reaches 93% (for 2kVA/ 3kVA). The 

unit not only protects your electrical equipment by providing secure and reliable 

uninterruptable power supply but also produces greater electric power efficiency 

at less cost.
The Amplon Family R series UPS is a light, compact and easy to use solution for 

IT applications and features rated nominal power capacities of 1kVA, 2kVA and 

3 kVA. Each kVA model has no internal battery but can be connected to at least 

one external battery pack (user-supplied).

Safety Instructions

2

z

z

Placement and Installation

1.  Read the Quick Guide carefully to ensure correct and safe usage of the 

product.

2.  Install the UPS in a well-ventilated area, away from rain, excess moisture, 

dust, flammable gas or explosives.

3.  To reduce the risk of fire or electric shock, install the UPS in a 

temperature and humidity controlled indoor area free of conductive 
contaminants. Please refer to 

10

Technical Specifications

 for operating 

temperature and relative humidity.

4.  Leave adequate space at least 15cm around each side of the UPS for 

proper ventilation.

z

z

 Connection  warnings

1.  Make sure the UPS is well grounded to avoid a possible risk of current 

leakage.

2.  The installation of protective devices (a DC non-fuse breaker or a DC 

fuse) is highly recommended when the UPS is connected to the power 

source and critical loads. 

3.  The protective devices connecting to the UPS must be installed near the 

UPS and must be easily accessible for operation.

4.  Do not use extension cord to connect the UPS to an AC outlet. 
5.  Do not plug the UPS input power cord into its own output receptacles.
6.  Prior to moving or reconnecting the UPS, disconnect the AC input power 

and ensure the UPS is powered off; otherwise, hazardous voltage may 

still exist at the output receptacles of the UPS, which presents a possible 

risk of current leakage.

7.  If you don't use the output power cord came with the UPS, please ensure 

the length of the output power cord is shorter than 10m.

z

z

Usage warnings

1.  The UPS is an EMC Class A product, which may cause wireless interference 

in your living environment. Precautions need to be taken to prevent possible 

interference.

2.  The UPS can be used to power computers and associated peripheral devices, 

such as monitors, modems, cartridge tape drives, external hard drives, etc.

3.  It is strictly forbidden to connect the UPS to:

-  regenerative loads

-  loads with half-wave controlled rectifier circuit

-  loads with asymmetrical current

4.  The external slits and openings in the UPS are provided for ventilation. To 

ensure reliable operation of the UPS and to protect the UPS from overheating, 

these slits and openings must not be blocked or covered.

5.  Before usage, you must allow the UPS to adjust to room temperature 

(20°C~25°C) for at least one hour.

6.  Do not splash any liquid on the UPS and be sure to prevent any foreign 

material from dropping into the UPS. Do not put beverages on or nearby the 

UPS.

7.  In an emergency, hold and press the 

OFF

 button, and release the button after 

you hear one beep to turn off the UPS. Meanwhile, cut off the mains to shut 

down the UPS.

8.  Never use cleaning liquid or spray to clean the UPS. Before cleaning, make 

sure you have (1) completely shut down the UPS, (2) unplugged the UPS 

from the power outlet, and (3) disconnected the unit from the external battery 

pack(s).

9.  Only qualified personnel can perform maintenance service. Do not open or 

remove the covers or panels of the UPS to avoid high voltage electric shock. 

10. You must contact Delta customer service if either of the following events 

occur:

-  Liquid is poured or splashed on the UPS.
-  The UPS does not run normally after carefully following the instructions in 

this Quick Guide.

z

z

 Battery  Precautions

1.  Do not dispose of the battery or batteries in a fire. The batteries may explode. 

Do not open or damage the battery or batteries. The released electrolyte is 

harmful to the skin and eyes and may be toxic.

2.  Servicing batteries and battery packs should be performed or supervised by 

qualified service personnel who are knowledgeable in batteries, battery packs 

and the required precautions. 

3.  The risk of dangerous voltage is possible when the batteries are still 

connected to the UPS even though the UPS is disconnected from the mains. 

Do not forget to disconnect the battery cable to completely cut off the battery 

source. 

4.  Only use the same type of batteries from the same supplier. Never use old, 

new and different Ah batteries at the same time.

5.  A battery can present a risk of electrical shock and high short circuit current. 

The following precautions should be observed when working on batteries:

-  Remove watches, rings or other metal objects.
-  Use tools with insulated handles.
-  Wear rubber gloves and boots.
-  Do not lay tools or metal parts on top of batteries.
-  Disconnect the charging source prior to connecting or disconnecting 

battery terminals.

6.  Do not reverse or short circuit the po and – when connecting the 

batteries because this will destroy the device and constitute a risk of electric 

shock or fire.

WARNING:

1.  Even though the UPS is disconnected from the mains, a battery may 

still present electrical shock and short circuit current hazard. Ensure to 

cut off the battery source prior to the UPS maintenance.

2.  When the external battery pack(s) is(are) connected to the UPS, the 

installation of the protective devices (a DC non-fuse breaker or a DC 

fuse) is required to protect the unit.

Standard Compliance

3

z

z

CE

z

z

IEC/ EN 62040-1

z

z

IEC/ EN 62040-2 Category C2

Packaging List

4

The UPS package contains the following items. Please check if any item is missing. If 

there is anything missing, please immediately contact the dealer.

z

z

UPS102/ 202/ 302R2002N035

×4

×4

×4

×2

Delta UPS - Amplon Family

R Series, Single Phase

1/ 2/ 3 kVA

Installation & Operation Quick Guide

ENGLISH

1

3

4

6

8

2

5

7

9

10

ON

OFF

SETU

P

No.

Item

Q’ty

1K

2/ 3K

1

UPS

1 PC

2

Installation & Operation Quick Guide

1 PC

3

Battery Wire

1 PC

4

Bracket Ear

1 SET

5

Battery Cable Tie

1 SET

6

USB Cable

1 PC

7

Input Power Cord 10A

1 PC

8

Input Power Cord 16A

1 PC

9

Output Power Cord 10A

1 PC

10

Output Power Cord 16A

1 PC

z

z

UPS102/ 202/ 302R2002N0B6

×4

×4

×4

×2

Delta UPS - Amplon Family

R Series, Single Phase

1/ 2/ 3 kVA

Installation & Operation Quick Guide

ENGLISH

1

3

4

6

8

2

5

7

9

10

ON

OFF

SETU

P

No.

Item

Q’ty

1K

2/ 3K

1

UPS

1 PC

2

Installation & Operation Quick Guide

1 PC

3

Battery Wire

1 PC

4

Bracket Ear

1 SET

5

Battery Cable Tie

1 SET

6

USB Cable

1 PC

7

Input Power Cord 10A

1 PC

8

Input Power Cord 16A

1 PC

9

Output Power Cord 10A

1 PC

10

Output Power Cord 16A

1 PC

z

z

UPS102/ 202/ 302R2002N0B0

Delta UPS - Amplon Family

R Series, Single Phase

1/ 2/ 3 kVA

Installation & Operation Quick Guide

ENGLISH

1

3

4

6

2

5

7

×4

×4

×4

×2

8

ON

OFF

SETU

P

No.

Item

Q’ty

1K

2/ 3K

1

UPS

1 PC

2

Installation & Operation Quick Guide

1 PC

3

Battery Wire

1 PC

4

Bracket Ear

1 SET

5

Battery Cable Tie

1 SET

6

USB Cable

1 PC

7

Input Power Cord 10A

1 PC

8

Input Power Cord 16A

1 PC

Rear Panel

5

UPS102R2002N035 & UPS102R2002N0B6

UPS102R2002N0B0

UPS202R2002N035 & UPS202R2002N0B6 & UPS302R2002N0B6

UPS202R2002N0B0 & UPS302R2002N0B0

UPS302R2002N035

R

S-

23

2

INPUT BREAKER

      250Vac.10A

  AC INPUT

MINI SLOT

OUTPUT SOCKET

EXTERNAL BATT. CONNECTOR

24V DC 40A

R

S-

23

2

INPUT BREAKER

      250Vac.10A

  AC INPUT

MINI SLOT

OUTPUT SOCKET

EXTERNAL BATT. CONNECTOR

24V DC 40A

R

S-

23

2

MIN

I SL

O

T

IN P U T  B R E A K E R

250V AC.20A

AC  IN P U T

   

 OUT

P

UT

 SO

C

KE

T

10A

 M

AX.

 P

ER

 OUTL

E

T

EXTERNAL BATT. CONNECTOR

48V DC 40A

R

S-

23

2

MIN

I SL

O

T

EXTERNAL BATT. CONNECTOR

48V DC 40A

IN P U T  B R E A K E R

250V AC.20A

AC  IN P U T

OUTPUT SOCKET

10A

 M

AX.

 P

ER

 OUT

LE

T

R

S-

23

2

MIN

I SL

O

T

   

  U

P

O

U

TP

U

TER

M

IN

AL

 B

LOC

K

EXTERNAL BATT. CONNECTOR

72V DC 40A

IN P U T  B R E A K E R

250V AC.20A

AC  IN P U T

   

 OUT

P

UT

 SO

C

KE

T

10A

 M

AX.

 P

ER

 OUTL

E

T

L

N

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

9

9

Continue to the Next Page

 



5013251901

Summary of Contents for ups302R2002N035

Page 1: ...occur Liquid is poured or splashed on the UPS The UPS does not run normally after carefully following the instructions in this Quick Guide z z Battery Precautions 1 Do not dispose of the battery or batteries in a fire The batteries may explode Do not open or damage the battery or batteries The released electrolyte is harmful to the skin and eyes and may be toxic 2 Servicing batteries and battery p...

Page 2: ... z z Turn Off Press and hold the button for 3 seconds and release it after you hear one beep z z Fault Clear When the UPS has a fault condition press and hold the button for 3 seconds release it after you hear one beep and the UPS will clear the fault condition NOTE When the UPS clears the fault condition it means that the buzzer warning message has been turned off To eliminate the fault detected ...

Page 3: ... 2 4 5 6 1 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or Original Display Inverter Frequency Setup Frequency Converter Setup Standby Bypass Setup ECO Setup Overload Alarm Setup Buzzer Setup Bypass Range Setup Battery String Setup Battery Capacity Setup Auto Start To On line Setup Power Factor Setup Restore Default Setup Inverter Voltage Setup NOTE 1 In ...

Page 4: ...battery mode for a specific time Please contact service personnel SD4 Battery Low Shutdown The UPS transfers into battery mode due to AC utility abnormality However the battery power is almost used up 1 Check the main AC source and the status of the input power cord 2 Please contact service personnel SD5 Cold Start Battery Empty Shutdown The batteries are damaged or battery lifetime is due Please ...