background image

www.deltapowersolutions.com 

2 / 4

No.

Item

Functions

1

RS-232 Port

For communicating with a PC to monitor the status of the UPS. UPSentry 2012 

Software is required. Please download it from http://www.deltapowersolutions.

com/en/mcis/software-center.php.

NOTE:

 Do not use the USB port and the RS-232 port at the same time. 

If you connect the USB cable to the USB port, the RS-232 port will be 

disabled right away.

2

USB Port

3

Fan(s)

For cooling and ventilation purpose.

4

Input Breaker

Prevents the UPS from damage caused by high current and protects the utility 

power from further damage when the UPS fails.

5

AC Input 

(Input Socket)

Connects the UPS to the mains. 

6

Mini Slot

Connects to a Mini SNMP, Mini Relay I/O or Mini MODBUS card (optional) to 

manage the UPS over the network.

7

External Batt. 

Connector

Connects to the external battery pack(s) to extend back up time (+, -, and    

terminals are included).

1 kVA : 24Vdc.40A 

2 kVA : 48Vdc.40A

3 kVA : 72Vdc.40A

8

Output Socket 

& UPS Output 

Terminal Block

Connects the loads to the UPS. The UPS output terminal block is only applicable 

for UPS302R2002N035.

9

Anti-Insect Net 

Mounting holes

For mounting the anti-insect net (optional) to prevent insects from entering into 

the UPS.

Only applicable for the UPS models ending with suffix B0 (UPS102R2002N0B0, 

UPS202R2002N0B0, and UPS302R2002N0B0).

Operational Panel

6

ON

OFF

SETUP

Hz
KW

KVA

AH

MIN

MIN

ECO

V

V%

IN

SET IN OUT BATT

RUN TIME

°C

LOAD TEST

6.3  LCD Display

6.2  Multi-function Buttons

6.1  LED Indicators

6.4  7-segment Display

6.5  16-segment Display

6.1  LED Indicators

Icon(s)

Description

Indicates the output status.

z

z

ON

 (green): Output; 

OFF

: No output.

1. 

ON

: The UPS detects an internal fault or an environmental fault. The error code will appear 

on the 16-segment display.

2. 

Flashing

: When the icon is flashing, it would be accompanied with other icon(s) to indicate 

the according warning message(s). 

For example: 

a. ( 

Hz
KW

KVA

AH

MIN

V

%

SET IN OUT BATT

°C

LOAD

TEST

 ): There is no battery or battery replacement is required.

b. ( 

Hz
KW

KVA

AH

MIN

V

%

SET IN OUT BATT

°C

LOAD

TEST

 ): Overload. 

c. ( 

MIN

V

IN RUN TIME

 ): Charging voltage is too high or too low.

6.2  Multi-function Buttons

Icon(s)

Description

z

z

Buzzer Off

: When the buzzer is on, press the button for 0.1 second to turn the buzzer off.

In setup mode, the button is used to confirm or change your parameter. For more details, 

please refer to 

6.2.1 Setup Mode

.

ON

z

z

Turn On

: Press and hold the button for 3 seconds, and release it after you hear one beep.

z

z

Battery Test

: Only applicable for on-line mode. Press and hold the button for 3 seconds, 

and the UPS will transfer into battery mode to perform a battery test. After the battery test 

completes, the LCD will show the test result and the UPS will return to on-line mode auto-

matically.

NOTE:

 The UPS will not perform the battery test if the batteries are not fully 

charged.

z

z

Scrolling Up/ Increasing Number

: Press the button for 0.1 second to go to the previous 

display or to increase number. In setup mode, press the button for 0.1 second to go to the 

previous parameter.

OFF

z

z

Turn Off

: Press and hold the button for 3 seconds, and release it after you hear one beep.

z

z

Fault Clear

: When the UPS has a fault condition, press and hold the button for 3 seconds, 

release it after you hear one beep and the UPS will clear the fault condition.

NOTE:

 When the UPS clears the fault condition, it means that the buzzer/ warning 

message has been turned off. To eliminate the fault detected, please refer 

to 

8

Troubleshooting

 for relevant solutions. 

z

z

Scrolling Down/ Decreasing Number

: Press the button for 0.1 second to go to the next 

display or to decrease number. In setup mode, press the button for 0.1 second to go to the 

next parameter.

ON

SETUP

z

z

Entering into the setup mode

Press the 

 and 

ON

 buttons at the same time for 3 seconds and the UPS will enter 

into the setup mode.

z

z

Exiting from the setup mode

When the UPS is in setup mode, press the 

 and 

ON

 buttons at the same time for 3 

seconds to exit the setup mode.

NOTE: 

1.  When the LCD display gets dim, press any of the above-mentioned buttons to wake up the LCD 

display and enable each button function.

2.  Only qualified service personnel can perform setup action.

3.  For more information about the setup mode, please refer to 

6.2.1 Setup Mode

.

6.2.1  Setup Mode

Please note that only qualified service personnel can perform setup action. In setup mode, you can set up the 

following items. For some settings, they can’t be set in certain operation modes. Please refer to the table below 

for relevant information.

Setup Item

Standby 

mode

On-line 

mode

Bypass 

mode

Battery 

mode

ECO

mode

Frequency  

converter  

mode

The code 

shown on the 

16-segment 

display

Meaning

INV *

1

Inverter Voltage  

Setup

V

X

V

X

X

X

INV *

1

Inverter 

Frequency  

Setup

V

X

V

X

X

X

COV

Frequency 

Converter Setup

V

X

V

X

X

X

STB

Standby Bypass  

Setup

V

V

V

V

V

V

ECO

ECO Setup

V

V

V

V

V

X

Setup Item

Standby 

mode

On-line 

mode

Bypass 

mode

Battery 

mode

ECO

mode

Frequency  

converter  

mode

The code 

shown on the 

16-segment 

display

Meaning

ALM

Overload Alarm  

Setup

V

V

V

V

V

V

BUZ

Buzzer Setup

V

V

V

V

V

V

BYP

Bypass Range  

Setup

V

V

V

V

V

V

CAP

Battery Capacity  

Setup

V

V

V

V

V

V

STG

Battery String  

Setup

V

V

V

V

V

V

AST

Auto-Start To On-

line Setup

V

X

V

X

X

X

PF

Power Factor  

Setup

V

X

V

X

X

X

RST

Restore Default  

Setup

V

X

V

X

X

X

NOTE: 

*

1

 

Both of the '

Inverter Voltage Setup

' and '

Inverter Frequency Setup

' use the same code, but you 

can tell whether the UPS is in '

Voltage

' or in 

'Frequency

' setup by checking the information shown 

on the 7-segment display.

The table below lists each setup item's setting parameters. 

Setup Item

Setting Parameters*

1

The code 

 shown on the  

16-segment 

display

Meaning

INV

Inverter Voltage Setup

200V, 208V, 220V (Default), 230V, 240V

INV

Inverter Frequency Setup

50Hz (Default), 60Hz

COV

Frequency Converter Setup

OFF (Default), ON

*

2

STB

Standby Bypass Setup

OFF, ON (Default)

*

3

ECO

ECO Setup

OFF (Default), ON

ALM

Overload Alarm Setup

60%, 70%, 80%, 85%, 90%, 95%, 100%, 105% (Default)

BUZ

Buzzer Setup

ENA (Enable) (Default), DIS (Disable)

BYP

Bypass Range Setup

5%, 6%, 7%, 8%, 9%, 10%, 11%, 12%, 13%, 

14%, 15% (Default), HI1, HI2, HI3

*

4

CAP

Battery Capacity Setup

0AH (Default), 5AH, 7AH, 9AH, 12AH, 15AH,  

24AH, 33AH, 38AH, 40AH, 50AH, 65AH,  

80AH, 100AH, 120AH, 150AH, 200AH

*

5

STG

Battery String Setup

0 (Default), 1, 2, 3, 4, 5, 6, 7, 8, 9

*

5

Continue to the Next Page

 



Summary of Contents for ups302R2002N035

Page 1: ...occur Liquid is poured or splashed on the UPS The UPS does not run normally after carefully following the instructions in this Quick Guide z z Battery Precautions 1 Do not dispose of the battery or batteries in a fire The batteries may explode Do not open or damage the battery or batteries The released electrolyte is harmful to the skin and eyes and may be toxic 2 Servicing batteries and battery p...

Page 2: ... z z Turn Off Press and hold the button for 3 seconds and release it after you hear one beep z z Fault Clear When the UPS has a fault condition press and hold the button for 3 seconds release it after you hear one beep and the UPS will clear the fault condition NOTE When the UPS clears the fault condition it means that the buzzer warning message has been turned off To eliminate the fault detected ...

Page 3: ... 2 4 5 6 1 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or 7 8 or Original Display Inverter Frequency Setup Frequency Converter Setup Standby Bypass Setup ECO Setup Overload Alarm Setup Buzzer Setup Bypass Range Setup Battery String Setup Battery Capacity Setup Auto Start To On line Setup Power Factor Setup Restore Default Setup Inverter Voltage Setup NOTE 1 In ...

Page 4: ...battery mode for a specific time Please contact service personnel SD4 Battery Low Shutdown The UPS transfers into battery mode due to AC utility abnormality However the battery power is almost used up 1 Check the main AC source and the status of the input power cord 2 Please contact service personnel SD5 Cold Start Battery Empty Shutdown The batteries are damaged or battery lifetime is due Please ...

Reviews: