38
Pr.45 Pr.46
Multi-function Output Terminal Setting
Parameter #
45 (MO1), 46(MO2)
Parameter Name
Multi-function photocoupled output terminals: MO1, MO2
Factory Setting
d0000, d0001
Units
None
Settings
d0000 AC drive operational
d0001 Pre-set frequency attained
d0002 Desired frequency attained
d0003 Count down complete
d0004 Non-zero speed
d0005 Over-torque detection
d0006 Baseblock indicator
d0007 Low-voltage detect indicator
d0008 AC drive operation mode
d0009 Fault indicator
Control terminals MO1 and MO2 are open collector outputs. Terminal MCM is
signal return (refer to Control Terminal Block description).
Description
AC drive operational
: This terminal will be “closed” when there is output from the
AC drive or when the FWD or REV run command is input.
Pre-set frequency attained
: This terminal will be “closed” once the AC drive
attained the specified operating frequency.
Desired frequency attained
: This terminal will be “closed” once the AC drive
attained the desired operating frequency.
Count down complete
: This terminal will be “closed” when the AC drive’s internal
counter, triggered by the external input TRG, starts countdown and reaches d0001.
Set the count down value using Pr.63 and Pr.66.
Non-zero speed
: This terminal will be “closed” when the AC drive output frequency
is greater than the minimum output frequency.
Over-torque detection
: This terminal will remain “closed” as long as over-torque is
detected. Set the over-torque detection level using Pr.61 and the over-torque
detection time using Pr.62.
Baseblock indicator
: This terminal will always be “closed” as long as the AC drive
output is turned off.
Low-voltage detect indicator
: This terminal will be “closed” when the AC drive
detects a low voltage state.
AC drive operation mode
: This terminal will be “closed” when the AC drive is
operated by commands via the RS-485 serial interface or control terminals.
Fault indicator
: This terminal will be “closed” when a major fault is detected.
Please see
descriptions below.