background image

2

www.deltatrak.com

     

     

Control Buttons

    

   The device has four buttons from left to right in this order:

       •  Clear Button 
           Use to clear the Alarm indication, the Max-Min memory or a setpoint 
           value during device configuration
       •  Mode 
           Use to switch between Max-Min and High-Low view modes or enter the 
           Configuration menu
       •  Up Arrow 
           Use to increase a set point value or recall the last alarm trigger reading
       •  Down Arrow 
           Use to decrease a set point value

       Note: The instrument has no power off button, so if it needs to be stored 

                without power then the battery must be removed

1. Configuration Menu Index
2. Max-Min Reset Icon
3. Alarm Icon
4. Battery Level Indicator
5. Current Temperature Reading
6. Temperature Scale Icons
7. Max-Min, High-Low Icons
8. Max-Min, High-Low Readings

Liquid Crystal Display (LCD)

     

Display Modes

        •  Max-Min Reading
            The LCD displays the current temperature reading, the maximum  
            reading and minimum readings. This is the default operation mode.

Basic Features

Summary of Contents for FlashCheck 12237

Page 1: ...Model 12237 User Guide Certified Min Max Alarm Thermometer...

Page 2: ......

Page 3: ...y LCD Control Buttons Basic Features Display Modes Changing the Display Modes Resetting the Min Max Readings Clearing the Alarm Indication Configuring the Thermometer Entering the Configuration Mode N...

Page 4: ...door located on the back side of the enclosure by removing the retaining screw Observe and follow the battery polarity Insert the battery into the battery holder The LCD will light up and you will hea...

Page 5: ...rigger reading Down Arrow Use to decrease a set point value Note The instrument has no power off button so if it needs to be stored without power then the battery must be removed 1 Configuration Menu...

Page 6: ...Max Min memory Alarm Indication Alarm indication must be enabled in the configuration menu and the High Low Alarm set points must be set When the sensor s reading exceeds the Alarm set points Alarm co...

Page 7: ...arm setting or click the Clear button to set it to zero Alarm Delay Menu 3 The alarm indication can be delayed after a number of consecutive readings in alarm up to 199 readings The delay setting is d...

Page 8: ...currently seleced scale Battery replacement The Thermometer can operate with low battery indication for at least 10 days During that time only one bar is visible on the battery level indicator When no...

Page 9: ...y Control Button Default Screen Configuration Mode Screen CLEAR If an Alarm has been triggered pressing CLEAR resets the Alarm indicator Bell icon and clears the High Low flashing indicator from the d...

Page 10: ...Menu option 4 3 Alarm Delay 0 Select up to 199 consecutive 30 second delay intervals 4 Enable Alarm On or Off On On Alarm is enabled The Menu Options 1 2 become operational When an Alarm is triggered...

Page 11: ...8 www deltatrak com Notes...

Page 12: ...ll at its option either repair or replace hardware products that prove to be defective if a notice to that effect is received within the warranty period DeltaTrak makes no other warranties or represen...

Reviews: