- 113 -
Auxiliary Timer Settings Menu
DEMA CPM 310 G Overcurrent Protection Relays are
equipped with 2 independent auxiliary timers. These
timers are set to trip the circuit breaker by default, but
can be utilized for wide range of applications.
Auxiliary timers can be triggered via inputs that are
programmed as
Start tAux1
or
Start tAux2
, and can
trigger outputs programmed as
tAux1
or
tAux2
. Note
that the auxiliary timers can be triggered only
externally via dedicated inputs; e.g. by a button that
energizes an input, to which
StartAux1
function is
assigned; or, by a programmable output relay.
The setting range for auxiliary timers is (0.0 - 600.0) s.
□
Main Screen » Menu »
Automatic Control Settings »
Auxiliary Timer Settings