- 93 -
Auto-Recloser (ARCL) Measurements Menu
Auto-Recloser
(ARCL)
Measurements Menu
is intended
to be used by statistical and diagnostic means; therefor
all values displayed on the menu can be reset when
needed. E.g., pressing S3 (Reset) button while at the
menu shown on the top picture will reset the
Total
Cycle
s measurement value. This action is applicable for
all measurements on the menu.
The measurements available on the menu are
described below.
Total Cycles Measurement
This measurement is the summation of the values of
1
st
, 2
nd
, 3
rd
and 4
th
cycle measurements and represents
the total number of CB closing commands generated by
the auto-recloser function.
1
st
, 2
nd
, 3
rd
and 4
th
Cycle Measurements
These values give the total CB closing commands
generated by the auto-reclose function for each of the
cycles.
ARCL Blocks Measurement
This measurement displays the total number of the
instances that auto-recloser is blocked.
Having examined the explanations above, the following example tries to figure the behavior of the
ARCL
(Auto-Recloser)
Measurements Menu
when an auto-recloser session is completed. The example
below is given presuming that the CPM 310 G unit is configured to make two auto-reclose shots when
the CB is tripped by I>> function.
5
1.
When the CB is tripped by the I>> function, the auto-recloser would conduct a reclose shot.
2.
If the failure is detected again, the CB will be tripped by the I>> function again, and the
auto-recloser will conduct a second reclose shot.
3.
If the failure is detected for the third time, the CB will be tripped and the auto-recloser will be
blocked.
For a scenario as above, formerly reset measurements will read as following:
Total Cycles
00002
1
st
Cycle
00001
2
nd
Cycle
00001
3
rd
Cycle
00000
4
th
Cycle
00000
ARCL Blocks
00001
□
5
For detailed information on the configuration of auto-recloser, please refer to the
Auto-recloser
Settings Menu
Section on this Manual.
Main Screen » Menu »
Measurements » ARCL
Measurements
Summary of Contents for CPM 310 G
Page 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Page 2: ...2...
Page 6: ...6 ABOUT DEMA...
Page 11: ...11 INTRODUCTION...
Page 32: ...32 PACKING LABELING INFORMATION...
Page 34: ...34 OPERATING MANUAL...
Page 53: ...53 RELAY MENUS MANUAL...
Page 55: ...55 The Menu Tree...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Page 189: ...189 APPLICATION DIAGRAMS...
Page 191: ...191 Sample Power Transformer Protection Application Diagram...
Page 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Page 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Page 204: ...204 TECHNICAL DATA...
Page 220: ...220 GLOSSARY...