Shanghai Denair Compressor Co.,Ltd.
www.denaircompressor.net 24/48
Parameter item
Set initial value
Functions
Air-end rated current
Motor ‘s allowed
maximum overload
value
1.2
╱
After start delaying
,
When the motor current value
greater than 1.2 times and below 4 times that of set value
,
please delay the machine jumping according to overload
characteristic.
Fan rated current
Motor ‘s allowed
maximum overload
value
1.2
╱
ditto
Air exhausting early
warning temperature.
105
℃
When the actual exhaust temperature higher than the set
temperature
,
prompt warning.
Air exhausting early
warning temperature
110
℃
When the actual exhaust temperature higher than this set
temperature
,
early warn the machine stop.
Air supplying stop
pressure
1.00MPa
When the actual air supplying pressure higher than the set
pressure
,
give stop warning.
Unloading pressure
upper limit
0.80MPa
In user parameter
,
the pressure upper limit set should be
less or equal to the set value.
Alter loading time
****hour
Manufacturers can modify loading operation time
Alter running time
****hour
Manufacturers can modify the total operating time
History fault reset
****
After Inputting history fault password
,
the faults will be
completely cleared out.
Current imbalance
degrees
0006
When (the maximum phase current
minimum phase
╱
current )
(1 + (S
≯
et value /10
)
〕
,
the imbalance
protection action stops
。
When set value
≥
15
,
the
imbalance protection is useless.
Continuing phase
protection time
0005
When open phase time set greater or equal with
20seconds
,
the Phase doesn’t work
。
If imbalance
protection works
,
the imbalance protection will act
。
Overload restart delay
0000minute
If motor overloading stop
,
only start the machine by time
delay no matter power down or reset to avoid the motor
frequent starting.
date of production
****year**month**day
The production date of the manufacturer input device
Factory number
******
The factory number of the manufacturer input device
Frequency changer
Model
********
Manufacturers supply it according to customers'
requirements.
Integral range
00.20MPa
Integral initial value
0020
Proportional gain
0010
Integral gain
0010
Differential gain
0000
standby
000.0
Set by machine type
Frequency lower limit
00.0Hz
Set by machine type