Commissioning
Multi
MAXX
HD
32
PR-2007-0350-GB • Subject to modifications • R2-04/2016
The appropriate group address must be assigned on the control panel and the units of
a group.
Single group (without networking multiple unit groups)
•
On the control panel, set the address “0” (manufacturer's default setting).
•
On the unit PCB(s), set the address “0” (manufacturer's default setting).
Networking multiple groups
•
On the control panels and all unit PCBs assigned to the individual groups, set the
addresses 0-15. Each group is given its own address. The labels A to F correspond
to the addresses 10 to 15.
MATRIX
2001
3001
9
NOTE!
Assigning duplicate addresses on the control panels causes malfunctions.
The default setting for the group address switch is “0” and it may need to be
changed, if necessary.
Fig. 10-4: Setting the address on the control panel
1: Control panel, unit(s)
Multi
MAXX
®
Group 0 (address 0)
2: Control panel, unit(s)
Multi
MAXX
®
Group 1 (address 1)
3: Control panel, unit(s)
Multi
MAXX
®
Group 2 (address 2) and so on
1
3
2
Group addresses:
0
Group 0
8
Group 8
1
Group 1
9
Group 9
2
Group 2
A
Group 10
3
Group 3
B
Group 11
4
Group 4
C
Group 12
5
Group 5
D
Group 13
6
Group 6
E
Group 14
7
Group 7
F
Group 15
Control panel
Unit printed circuit
board