115
Appendix E—Calculated Power Channel Formulas
The following information details the formulas used to calculate the parameters available in the Power
Sum Channels 5 and 6.
W
YE
C
ONFIGURATION
L1-N,
L2-N,
L3-N
Measurement
Formula
Notes/Description
Amps (System)
L1 + L2 + L3
3
Average of L1, L2, and L3 amp values.
Volts (System )
Sum of three phase to neutral voltages
3
For a Phase to Neutral with WYE
configured meter.
Average of the three phase-to-neutral
voltages.
kW (System)
L1 kW + L2 kW + L3 kW
Sum of L1, L2, and L3 phase watt
values.
kWh (System)
L1 kW + L2 kW + L3 kW
# of samples in an hour
Calculated per waveform sample with
a running total of each waveform kWh
for the integration period.
VAR (System)
L1 kVAR + L2 kVAR + L3 kVAR
VARh (System)
L1 kVAR + L2 kVAR + L3 kVAR
# of samples in an hour
See kWh (System) WYE notes.
VA (System)
L1 kVA + L2 kVA + L3 kVA
VAh (System)
L1 kVA + L2 kVA + L3 kVA
# of samples in an hour
See kWh (System) WYE notes.
Apparent PF System
kW System
kVA System
Measurement calculation information
is provided for reference only.
Displacement PF System
kW System
SQRT [(kW System)
2
+ (kVAR System)
2
]
www.
.com
information@itm.com
1.800.561.8187
Summary of Contents for ELITEpro XC
Page 58: ...58 Typical Single Phase 2 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Page 59: ...59 Typical Single Phase 3 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Page 60: ...60 Typical 3 Phase 3 Wire Delta Setup Diagram www com information itm com 1 800 561 8187 ...
Page 61: ...61 Typical 3 Phase 4 Wire Wye Setup Diagram www com information itm com 1 800 561 8187 ...