26
V
OLTAGE
C
ONNECTIONS
1) Before connecting voltage leads L1, L2, L3, & N to the
meter, first connect them to dedicated circuit
breakers using either Croc-clips or lead adapters from
DENT.
a) Refer to the wiring diagrams in Section 2 for
wiring connection specifics. Follow local electrical
codes during this installation.
b)
IMPORTANT:
Verify the breaker is marked as the
disconnect breaker for the
ELITE
pro
XC
.
2) Connect lead adapters to the banana sockets at the
end of the voltage leads.
3) Connect the voltage leads (L1, L2, L3, and N, as necessary) to the
ELITE
pro
XC
.
A
NALOG
C
HANNEL
C
ONNECTIONS
Analog inputs are especially helpful when used in conjunction with power measurements to correlate
the consumption of electricity with environmental, HVAC plant performance or other process
conditions. Typical uses might include logging ambient temperature, building temperatures, solar
insolation, tank pressures, duct flows, etc.
The
ELITE
pro
XC
has four analog input channels that can be configured for voltage or current input used
in any combination among channels. The limiting specifications for analog input are shown below.
Analog Input Technical Specifications
MAXIMUM INPUT VOLTAGE
30 VDC, Unipolar Measurements Only.
MAXIMUM INPUT CURRENT
23 ma
Note: the current limit will be exceeded before 30 volts of applied
potential when selected for current mode or connected with reverse
polarity.
A/D
16 bit
INPUT IMPEDANCE
50.0 K (voltage mode), 499 ohm (current mode)
SAMPLING FREQUENCY
4 HZ - per channel, 16 HZ total throughput
ACCURACY
<0.2% typical
D
ID
Y
OU
K
NOW
?
The
ELITE
pro
XC
is rated
for 600V Over-Voltage Category III. Cat
III is for measurements performed in the
building. Examples are measurements
on distribution boards, circuit-breakers,
wiring including cables, bus bars,
junction boxes, switches, and socket
outlets in a fixed installation, and
equipment for industrial use. Other
equipment could include stationary
motors with a permanent connection to
the fixed installation.
www.
.com
information@itm.com
1.800.561.8187
Summary of Contents for ELITEpro XC
Page 58: ...58 Typical Single Phase 2 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Page 59: ...59 Typical Single Phase 3 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Page 60: ...60 Typical 3 Phase 3 Wire Delta Setup Diagram www com information itm com 1 800 561 8187 ...
Page 61: ...61 Typical 3 Phase 4 Wire Wye Setup Diagram www com information itm com 1 800 561 8187 ...