21
DENT
Instruments
PowerScout 24
Prepping for Field Installation
Setting the Network Address Switches
There are three rotary decimal network address switches on the PowerScout 24 used to select the
BACnet/Modbus address the client uses to communicate with the PowerScout.
Figure 4: Rotary Decimal Address Switches
The BACnet MS/TP MAC and Modbus address is a decimal value, represented by three digits: 000
through 009, 010-090, and 100-999.
Note:
BACnet MS/TP masters only support addresses 001–127.
Decimal Address
BACnet Address Availability
000
Reserved for resetting the PowerScout to Modbus mode with 9600 baud,
8 bit, 1 stop bit and no parity.
001-127
Available (01/001 is the factory default setting).
128-254
Reserved for BACnet slave devices.
255
Reserved for network broadcast.
999
Used to configure PS24 for Modbus/BACnet
Table 2: BACnet Hexadecimal/Decimal Address Availability