Field Installation
Wiring Connections on a PowerScout Meter
High voltage MAY BE PRESENT. Risk of electric shock. Life threatening voltages may be present.
Qualified personnel only.
Haute tension peut être présente. Risque de choc électrique. Tensions dangereuses peuvent
être présentes. Personnel qualifié uniquement.
PowerScout 24 meters have the following connections:
Either a three-wire connector for the RS-485 BACnet/Modbus link or an Ethernet connector.
Four voltage connections, but the leads are customer supplied.
PowerScout meters are self-powered from L1 and L2.
Up to twenty-four current transformers (CTs).
Digital output ports. The ports can be used to output kWh, kVARh, or kVAh pulses to external
devices, or to toggle on and off to control a remote device or relay.
Completing the Field Installation
Follow these steps to complete the field installation of your PowerScout meter:
Connect whatever communications cable you are using to the building network.
Connect your pulse output, if used. The port can be used to output kWh, kVARh, or kVAh pulses
to external devices, or to toggle on and off to control a remote device or relay. See
Using the
Pulse Output Port Function.
Connect the CTs. See
Wiring CTs
.
Connect the voltage and power the meter. See
Connecting Voltage
.