70
DENT
Instruments
PowerScout 24
All Things Modbus
Modbus
Offset
Register
Description
* System=sum of three phases
46034
6033
Positive kVARh L2 LSW
“
46035
6034
Positive kVARh L2 MSW
“
46036
6035
Positive kVARh L3 LSW
“
46037
6036
Positive kVARh L3 MSW
“
46038
6037
Positive kVAR L1
Individual Phase Positive Instantaneous Reactive
Powers (kVAR)
46039
6038
Positive kVAR L2
“
46040
6039
Positive kVAR L3
“
46041
6040
kVAh L1 LSW
Individual Phase Apparent Energy LSW (kVAh,
resettable)
46042
6041
kVAh L1 MSW
Individual Phase Apparent Energy MSW (kVAh,
resettable)
46043
6042
kVAh L2 LSW
“
46044
6043
kVAh L2 MSW
“
46045
6044
kVAh L3 LSW
“
46046
6045
kVAh L3 MSW
“
46047
6046
kVA L1
Individual Phase Instantaneous Apparent Powers
(kVA)
46048
6047
kVA L2
“
46049
6048
kVA L3
“
46050
6049
Positive Displacement PF L1
Individual Phase Positive Displacement Power Factors
(dPF); Register is 100x actual value (If the Individual
dPF (44050) is positive, this register will contain that
value else it will be zero)
46051
6050
Positive Displacement PF L2
“
46052
6051
Positive Displacement PF L3
“