76
DENT
Instruments
PowerScout 24
All Things Modbus
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47082
7081
kVA Demand System Maximum Maximum Instantaneous kVA Demand (kW,
resettable).
47083
7082
kVA Demand System Now
System Average kVA Demand for the most recent
(current) Demand Window (resettable).
47084
7083
kVAR Demand System Max
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until 1 demand
window elapses. After a power cycle or CPU reset the
value is not reset but it does not update again until 1
demand window elapses.
N
ET
M
EASUREMENT
R
EGISTERS
Modbus
Offset
Register
Description
* System=sum of three phases
44150
4149
KWh System NET LSW
ABS of the NET System Total True Energy LSW (kWh)
44151
4150
KWh System NET MSW
ABS of the NET System Total True Energy MSW (kWh)
44152
4151
KWh L1 NET LSW
ABS of the NET L1 True Energy LSW (kWh)
44153
4152
KWh L1 NET MSW
ABS of the NET L1 True Energy MSW (kWh)
44154
4153
KWh L2 NET LSW
ABS of the NET L2 True Energy LSW (kWh)
44155
4154
KWh L2 NET MSW
ABS of the NET L2 True Energy MSW (kWh)
44156
4155
KWh L3 NET LSW
ABS of the NET L3 True Energy LSW (kWh)
44157
4156
KWh L2 NET MSW
ABS of the NET L3 True Energy MSW (kWh)
46150
6149
KWh System NET POS LSW
Positive of the NET System Total True Energy LSW
(kWh)
46151
6150
KWh System NET POS MSW
Positive of the NET System Total True Energy MSW
(kWh)
46152
6151
KWh L1 NET POS LSW
Positive of the NET L1 True Energy LSW (kWh)
46153
6152
KWh L1 NET POS MSW
Positive of the NET L1 True Energy MSW (kWh)
46154
6153
KWh L2 NET POS LSW
Positive of the NET L2 True Energy LSW (kWh)