90
DENT
Instruments
PowerScout 24
All Things BACnet
N
EGATIVE
P
OWER
/E
NERGY
M
EASUREMENT
O
BJECTS
Object
Identifier
Name
Detailed Description
* System=sum of three phases
1090
kW System Average Negative
Equals kWh System Negative / (Time Since Reset /3600 seconds/Hr)
(resettable)
1120
kW System Maximum Negative
System Highest Instantaneous Negative Draw Since Reset (kW)
1150
kW System Minimum Negative
System Lowest Instantaneous Negative Draw Since Reset (kW,
resettable)
2020
kWh System Total Negative
System True Energy (kWh) Negative (Signed Net)
2050
kWh L1 Negative
Individual Phase True Energy (kWh) (Signed)
2080
kWh L2 Negative
“
2110
kWh L3 Negative
“
6030
kVARh Sys Negative
System Total Reactive Energy (Signed Net)
6060
kVARh L1 Negative
Individual Phase Reactive Energy (kVARh) (Signed)
6090
kVARh L2 Negative
“
6120
kVARh L3 Negative
“
7002
kVAh System Total Negative
System Total Negative Apparent Energy (Signed Net)
7030
kVAh L1 Negative
Individual Phase Apparent Energy (kVAh) (Signed)
7060
kVAh L2 Negative
“
7090
kVAh L3 Negative
“