background image

4

101851

NATURAL GAS HEATER

VANGUARD VN6C AND VN10

WARNING: If the area in which

the heater may be operated is
smaller than that defined as an
unconfined space, provide ad-
equate combustion and ventila-
tion air by one of the methods
described in the 

National Fuel

Gas Code, ANSI Z223.1, 1992,
Section 5.3 or applicable local
codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR
FLOW FOR HEATER
LOCATION

Determining if You Have a
Confined or Unconfined Space

Use this worksheet to determine if you have
a confined or unconfined space.

Space:

 Includes the room in which you

will install heater plus any adjoining rooms
with doorless passageways or ventilation
grills between the rooms.

1.

Determine the volume of the space
(length x width x height).

Length x Width x Height =

__________ cu. ft. (volume of space)

Example:

Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) =
2560 cu. ft. (volume of space)

If additional ventilation to adjoining
room is supplied with grills or open-
ings, add the volume of these rooms to
the total volume of the space.

2.

Divide the space volume by 50 cubic
feet to determine the maximum Btu/Hr
the space can support.

________ (volume of space) 

÷

 50 cu.

ft. = (Maximum Btu/Hr the space can
support)

Example:

  2560 cu. ft. (volume of

space) 

÷

 50 cu. ft. =

51.2 or 51,200

(maximum Btu/Hr the space can sup-
port)

3.

Add the Btu/Hr of all fuel burning ap-
pliances in the space.

Vent-free heater __________ Btu/Hr

Gas water heater* ________ Btu/Hr

Gas furnace _____________ Btu/Hr
Vented gas heater _________ Btu/Hr
Gas fireplace logs ________ Btu/Hr
Other gas appliances*+ ____ Btu/Hr
Total                           = ____ Btu/Hr

Example:

Gas water heater       40,000

Btu/Hr

Vent-free heater  +    10,000

Btu/Hr

Total                    =    50,000 Btu/Hr

* Do not include direct-vent gas appli-
ances. Direct-vent draws combustion
air from the outdoors and vents to the
outdoors.

4.

Compare the maximum Btu/Hr the
space can support with the actual
amount of Btu/Hr used.

__________ Btu/Hr (maximum the

space can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

Example:

46,100 Btu/Hr (maximum

the space can support)

50,000 Btu/Hr (actual

amount of Btu/Hr used)

The space in the above example is a con-
fined space because the actual Btu/Hr used
is more than the maximum Btu/Hr the space
can support. You must provide additional
fresh air. Your options are as follows:

A. Rework worksheet, adding the space of

an adjoining room. If the extra space
provides an unconfined space, remove
door to adjoining room or add ventila-
tion grills between rooms. See Ventila-
tion Air From Inside Building, 
page 5.

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 5.

C. Install a lower Btu/Hr heater, if lower

Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the
maximum Btu/Hr the space can support, the
space is an unconfined space. You will need
no additional fresh air ventilation.

UNUSUALLY TIGHT
CONSTRUCTION

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is
defined as construction where:
a.walls and ceilings exposed to

the outside atmosphere have a
continuous water vapor re-
tarder with a rating of one perm
(6x10

-11

 kg per pa-sec-m

2

) or

less with openings gasketed or
sealed 

and

b.weather stripping has been

added on openable windows
and doors 

and

c.caulking or sealants are ap-

plied to areas such as joints
around window and door
frames, between sole plates
and floors, between wall-ceil-
ing joints, between wall panels,
at penetrations for plumbing,
electrical, and gas lines, and at
other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 5.

If your home does not meet all of the
three criteria above, proceed to 

Deter-

mining Fresh-Air Flow For Heater Lo-
cation.

Confined and Unconfined Space

The National Fuel Gas Code (ANSIZ2123.1,
1992 Section 5.3) defines a confined space
as a space whose volume is less than 50
cubic feet per 1,000 Btu per hour (4.8 m3 per
kw) of the aggregate input rating of all
appliances installed in that space and an
unconfined space as a space whose volume
is not less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that

space. Rooms communicating directly with
the space in which the appliances are in-
stalled*, through openings not furnished
with doors, are considered a part of the
unconfined space.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

Summary of Contents for Vanguard VN10

Page 1: ...as supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for ...

Page 2: ... shall not be in stalled in a bathroom 4 Never install the heater in a recreational vehicle where curtains furniture clothing or other flammable objects are less than 36 inches from the front top or sides of the heater as a fireplace insert in high traffic areas in windy or drafty areas 5 Always run heater with control knob at LOW or HIGH locked positions VN10 or ON position VN6C Never set control...

Page 3: ... cient than ever New materials increased insulation and new construction methods help reduce heat loss in homes Home own ers weather strip and caulk around windows and doors to keep the cold air out and the warm air in During heating months home owners want their homes as airtight as pos sible While it is good to make your home energy efficient your home needs to breathe Fresh air must enter your ...

Page 4: ...m Btu Hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet adding the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining room or add ventila tion grills between rooms See Ventila tion Air From Inside Building page 5 B Vent room directly to the outdoors See Ventilation Air From Outdoors page 5 ...

Page 5: ...entilation Grills Into Adjoining Room Option 2 12 12 Ventilation Grills into Adjoining Room Option 1 Figure 2 Ventilation Air from Inside Building VENTILATION AIR Ventilation Air From Inside Building Thisfreshairwouldcomefromanadjoining unconfined space When ventilating to an adjoining unconfined space you must pro vide two permanent openings one within 12 of the ceiling and one within 12 of the f...

Page 6: ...moisture See Air for Com bustion and Ventilation pages 3 through 5 Mounting Screw Locations 10 7 8 Minimum To Maintain 8 Clearance From Wall 7 3 4 20 1 4 Minimum To Maintain 3 Clearance From Floor FLOOR JOINING WALL INSTALLING TO WALL NOTICE A qualified service per son must install heater Follow all local codes CHECK GAS TYPE Use only natural gas If your gas supply is not natural do not install he...

Page 7: ...ote Do not replace front panel at this time Replace front panel after making gas connections and checking for leaks see pages 8 and 9 Figure 7 Popping Open Anchor Wings For Thin Walls Thin Walls 1 4 to 1 2 thick INSTALLING TWO MOUNTING SCREWS Note Wall anchors and mounting screws areinhardwarepackage Thehardwarepack age is provided with heater Attaching to wall stud method For attaching mounting s...

Page 8: ...essure must be no greater than 14 inches of water If gas line pressure is higher heater regulator damage could occur CAUTION Use only new black iron or steel pipe Inter nally tinned copper tubing may be used in certain areas Check your local codes Use pipe 3 8 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur Installation must include a...

Page 9: ...s meter 3 Check all joints from gas meter to manual shutoff valve see Figure 14 Apply mixture of liquid soap and wa ter to gas joints Bubbles forming show a leak 4 Correct all leaks at once CHECKING GAS CONNECTIONS WARNING Test all gas pip ing and connections for leaks after installing or servicing Cor rect all leaks at once WARNING Neveruseanopen flame to check for a leak Apply a mixture of liqui...

Page 10: ...n at the beginning of Oper ating Heater If you don t smell gas go to the next step 5 Press in control knob and turn coun terclockwise C clockwise to pilot posi tion Keep control knob pressed for five seconds Note You may be running this heater for the first time afterhook ing up to gas supply If so the con trol knob may need to be pressed in for 30 seconds This will allow air to bleed from the gas...

Page 11: ...erson Heater may need more frequent cleaning due to excessive lint from carpeting bedding material etc GRH OV 009 GOOD PILOT GRH OV 010 BAD PILOT If pilot flame pattern is incorrect as shown in Figure 19 turn heater off see To Turn Off Gas to Appliance page 10 see Troubleshooting pages 12 through 14 Pilot Burner Thermocouple Thermocouple Pilot Burner Check pilot flame pattern and burner flame patt...

Page 12: ... heater cabinet at top 6 Replace ignitor cable 7 Replace piezo ignitor 1 Turn on gas supply or open manual shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down control knob Repeat igniting operation until air is re moved 5 Clean ODS pilot see Cleaning and Maintenance page 11 or replace ODS pilot assembly 6 Replace gas regulator...

Page 13: ...ation 1 This is common with most heaters If noise is excessive contact qualified ser vice person POSSIBLE CAUSE 1 Burner orifice s is clogged 2 Burner orifice s diameter is too small 3 Inlet gas pressure is too low 1 Manifold pressure is too low 2 Burner orifice s is clogged 1 Burner orifice s is clogged or damaged 2 Inlet gas pressure is too low 3 Burner damaged 4 Gas regulator defective 1 Plaque...

Page 14: ...ff gas supply Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department POSSIBLE CAUSE 1 Heater burning vapors from paint hair spray glues etc See IMPORTANT statement above 2 Gas leak See Wa...

Page 15: ...ntact authorized dealer from whom you purchased this product If they cannot sup ply original replacement part s call DESA International s Technical Service Depart ment at 1 800 323 5190 for referral infor mation When contacting your dealer or DESA In ternational have ready your name your address model number of your heater how heater was malfunctioning type of gas used propane LPor natu ral gas pu...

Page 16: ...lectrode 1 8 099884 01 Burner Assembly 1 9 099056 04 Injector 1 10 099390 01 Tubing Valve to burner 1 11 099387 05 Pilot Tubing Valve to pilot 1 12 099391 02 Tubing Regulator to valve 1 13 100829 01 Control Valve 1 PARTS AVAILABLE NOT SHOWN KEY PART NO NUMBER DESCRIPTION QTY 14 099057 01 Pressure Tap Fitting 1 15 098276 01 1 8 Pipe Plug 1 16 099468 10 Cabinet Assembly 1 17 099415 01 Gas Regulator ...

Page 17: ...lowtheinstructionslisted under Replacement Parts on page 15 of this manual KEY PART NO NUMBER DESCRIPTION QTY 1 098304 01 Screw 10 x 3 8 2 2 099467 03 Front Panel Assembly 1 3 099318 03 Grill Guard 1 4 101108 01 Grill Guard Clip 2 5 099469 02 Reflector Assembly 1 6 M15823 37 Screw Hex 8 x 1 4 10 7 503329 ODS Pilot Assembly 1 7 1 098514 01 Thermocouple 1 7 2 098594 01 Ignitor Electrode 1 8 099884 0...

Page 18: ..._________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ ______________________________________________________________________________...

Page 19: ...____________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ ___________________________________________________________________________________________...

Page 20: ...any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIESANDLIMITSTHEDURATIONOFANYANDALLIMPLIEDWARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE T...

Reviews: