30
Figure 31
Figure 32
The Network Config screen shown in Figure 33 allows for the zone
temperature and relative humidity from one unit on the Ethernet
subnet to be sent to any other unit on that subnet. The first three
octets of the IP address must be the same as well. In order to
prevent network faults from shutting down the dehumidifier, DHCP
must be turned ‘Off’ and a static IP address must be used. Consult
with the system administrator for static IP addresses for all
dehumidifiers.
The fourth octet in the address is settable from 000 to 255. Set the
octet to the assigned address of the unit with the zone sensor that is
to be used. If data is being sent from that unit, the **NETWORK
FAULT** display will change to “Data is Being Sent”. Now the bottom
line of this screen can be modified from “Use Local Sensor” to “Use
Network Sensor”. Adjusting set points, deadbands, and differentials
will now allow the network sensor to control all dehumidifiers on the
network.
Desert Aire - CM3540 Manual