11
2 Installation
Manual applies to standard unit configurations only.
2.1
Location of Dehumidifier
Allow a minimum of 36 inches of clearance around all sides of the dehumidifier for piping,
duct connections, and service access. Install the unit on a sturdy, level mounting base or a
platform that will prevent vibration and sound transmission. Never install the dehumidifier on
a wooden platform without consulting the design engineer for spring isolation requirements
and sound control materials. Do not install the unit near occupied rooms such as offices or
guestrooms. Do not attempt to conserve installation space by fabricating restrictive ductwork
with abrupt bends. You may reduce the operating efficiency and the moisture removal
capacity of the dehumidifier. See section 2.2 for detailed duct installation instructions.
Figure 1 - Typical Floor Installation
Desert Aire - LW Manual