2.8.3.2 Outdoor Static Sensor
A complication in measuring the building static pressure is the dynamic action of the wind.
Measuring the wind’s pressure instead of the true outdoor static pressure will alter the actual
static pressure reading. Proper mounting of the outdoor static sensor will help ensure
accurate readings.
The outdoor air static pressure sensor should be mounted at least 12 inches above
surrounding obstacles and a minimum of 24 inches from a wall or Air Handling Unit. Do not
mount under awnings or other projections within fifteen feet. Do not mount near economizers,
intakes or exhaust fans, or barometric dampers. Do not mount within 10’ of building corners
or parapet walls.
Figure 18 – Outdoor Static Pressure Sensor
A detailed drawing of the outdoor static assembly is included within the package. Assemble
mounting bracket and tubing per this drawing. 50’ of 1/8” pressure tubing is supplied with the
sensor.