83
• Do not use acid neutralizing additives or other chemicals for acid removal. The
refrigeration system must contain only oil and refrigerant. Precipitates of additives and
acids may be considered contamination in the refrigeration system. Other compounds may
be present in additives as carriers. Longterm effects of specific additives or compounds
with a particular system or design are unknown without significant controlled testing.
Particulate
Indicated
• Install a replaceable core liquid line filter shell. Note that larger Desert Aire systems will
have replaceable core liquid filter shells installed from the factory. The pressure drop
levels will be monitored and several core changes may be required. Install ball valves on
either side of the filter shell to facilitate these changes.
• Install a secondary filter such as Sporlan FS-series or equivalent 20 micron filter in the
replaceable core.
• Ensure there are access fittings directly upstream and downstream of the liquid filter.
There is typically one fitting installed on the filter shell. There is typically one fitting installed
on the outlet side of the receiver.
Returning to Service
• See section 5.6 for evacuation and charging.
• Restart unit and set unit to run compressors.
• Record the pressure drop across the suction filter and liquid line filter dryer.
• Check sight glass indicator for moisture level.
• Monitor pressure drop across the liquid and suction filters during the first hour of operation.
Compare the reading taken earlier. If the pressure differential across the filters is 5 PSI or
greater than the initial reading, isolate the filters using the valves installed and recover the
refrigerant from the filters. Replace cores. If activated carbon filters were installed in the
suction side to remove acid, replace with similar cores. If a secondary filter was
installed in the liquid line core to remove particulate, install cores and secondary filter in
this location.
• Run unit for 24 hours and review acid levels (if found previously) and pressure differentials.
- If acid is found, replace with activated charcoal cores and test at 24 hour intervals
until acids are at acceptable levels. Once acid is no longer detected, replace cores
with standard filter elements. Remove outlet screens if they were required by filter
manufacturer.
- If the pressure differential across the liquid line filter is 5 PSI or greater, replace
cores and secondary filter with new components and test at 24 hour intervals until
pressure drop is at acceptable levels. Once pressure differential is less than 5
PSI, remove secondary filter and replace cores.
Testing and Final Diagnosis
It is of critical importance to ensure that the system is operating as expected before unit is returned
to normal service. Complete a Compressor Replacement Form located in the back of this manual.
Validation of this report allows for the continued coverage of the compressor under the original warranty.
It is possible that there was an internal defect in the compressor or normal mechanical wear occurred
Desert Aire - SP Manual
Summary of Contents for SelectAire Plus SP Series
Page 2: ...2 ...
Page 12: ...12 Desert Aire SP Manual ...
Page 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Page 101: ...101 Desert Aire SP Manual ...
Page 102: ...102 Desert Aire SP Manual ...
Page 103: ...103 Desert Aire SP Manual ...
Page 104: ...104 Desert Aire SP Manual ...
Page 105: ...105 Desert Aire SP Manual ...
Page 106: ...106 Desert Aire SP Manual ...
Page 109: ...109 Desert Aire SP Manual ...