Blast chiller Service Manual
3
Rev 07/04/2015
Parameter Description
5 PANS
115V
5 PANS
230V
SELF
CONTAINED
230V
TROLLEY
OF8
core probe point 5 offset [°C/°F]
0
0
0
0
SLL
not used
-40
-40
-40
-40
SLH
not used
3
3
3
3
RHU
cabinet RH% set point settable [num]
80
80
80
80
MNS
mains voltage alarm limit [%]
20
20
20
20
MAL
voltage alarm delay [hours]
10
10
10
10
MEV
max number of voltage conditions before voltage
alarm [num]
5
5
5
5
MBP
time range in which is performed the mains
voltage control [hours]
1
1
1
1
RL1
relay 1 action type [num]
1
1
1
1
RL2
relay 2 action type [num]
13
13
13
17
RL3
relay 3 action type [num]
17
17
17
13
RL4
relay 4 action type [num]
13
13
13
13
RL5
relay 5 action type [num]
0
0
0
0
RL6
relay 6 action type [num]
11
11
11
11
RL7
relay 7 action type [num]
10
10
10
10
RL8
relay 8 action type [num]
1
1
1
1
SRV
remaining time before maintenance [day]
800
800
800
800
PCA
cabinet set point in prechilling [°C/°F]
28
28
28
28
PCF
evaporator fan speed in prechilling [num]
10
10
10
10
PFA
cabinet set point in prefreezing [°C/°F]
-22
-22
-22
-22
PFF
evaporator fan speed in prefreezing [num]
10
10
10
10
DWA
load tolerance on relays [%]
20
20
20
20
STO
max storage time without hot gas defrost [hours]
48
48
48
48
DFS
difference between core probe and cabinet
probe to detect core probe inserted [°C/°F]
18
18
18
18
STE
sterilization cycle duration [sec]
300
300
300
300
PRH
heating core probe cycle duration [sec]
60
60
60
60
VOF
mains voltage sensor offset [num]
77
77
77
77
PTE
not used
20
20
20
20
PTI
not used
12
12
12
12
MRT
max recharging time of battery [hours]
20
20
20
20
FCD
max first recharging time of battery [hours]
12
12
12
12
BTD
max duration of battery test [sec]
3
3
3
3
TBT
consecutive battery test interval time [min]
5
5
5
5
NMT
not used
250
250
250
250
VRS
start battery charging threshold [V/10]
11,1
11,1
11,1
11,1
VRE
end battery charging threshold [V/10]
11,3
11,3
11,3
11,3
VRT
battery voltage at ending charging for max
duration [V/10]
9,8
9,8
9,8
9,8
VBR
minimum battery voltage for disabling battery
[V/10]
8,6
8,6
8,6
8,6
VAD
battery voltage threshold to show "no battery"
3,3
3,3
3,3
3,3
Summary of Contents for GBC-15
Page 1: ...Service Manual Blast Chiller...
Page 2: ...Rev 07 04 2015 2...
Page 3: ...Blast chiller Service Manual 3 Rev 07 04 2015...
Page 32: ...Rev 07 04 2015 32...
Page 40: ...Rev 07 04 2015 40...
Page 50: ...Rev 07 04 2015 10 20 10 0 10 20 30 40 kOhms C kOhmsVsTempChart NTC 10kOhms 25 C ZOOM...
Page 57: ...Blast chiller Service Manual 17 Rev 07 04 2015 L1 L2...
Page 91: ...Blast chiller Service Manual 51 Rev 07 04 2015 6 SCHEMATICS 6 1 SCHEME OF COMPONENTS...
Page 97: ...Blast chiller Service Manual 57 Rev 07 04 2015...
Page 100: ...Rev 07 04 2015 60...