28
STEP
DESCRIPTION
DISPLAY
CODE
AVAILABLE SETTINGS
FACTORY
SETTING
18
Display Enable
diSP
1 = Display Setpoint*
2 = Display Process
Variable
3 = Display Process
Variable** and Setpoint
4 = Display Blank
* If configured for both
high and low limit ,the
high limit setpoint will
be in the upper display
and the low limit in the
lower display.
** If configured for both
high and low limit,
pressing the up key
while in control mode
will display high limit
setpoint. Pressing the
down key will display
the low limit setpoint.
3
1
Applies only if process alarm is selected in Configuration mode.
2
Applies only if a linear input has been specified.
3
Only if an alarm is active.
NOTE: Euu and EuL parameters can not be adjusted within the range of the SPhi and
SPlo parameters of the Setpoint Change Mode. SPhi and SPlo may need to be
changed before properly setting Euu and EuL.
MAXIMUM/MINIMUM HOLD
A parameter is available that tracks and saves the maximum (high limit) or minimum
(low limit) excursions of the process variable.
This parameter is a read only parameter and is viewed in the Set-Up mode, display
code
HiHd
(maximum hold) and
LoHd
(minimum hold).
To reset this parameter, select the parameter and with the numeric value in the upper
display, press and hold the UP or DOWN keys. After about 5 seconds, the upper
display will indicate
----
for about another 2 seconds, then change to
0.00
. Release the
key.
The value will be held through a supply power down/power up cycle.
Summary of Contents for MIC 1162
Page 2: ......
Page 4: ...ii...
Page 8: ...4 FIGURE 2 1 Panel Cut Out Dimensions FIGURE 2 2 Main Dimensions...
Page 26: ...22...
Page 30: ...26...
Page 34: ...30...
Page 36: ...32...
Page 40: ...36...
Page 41: ...37 APPENDIX A BOARD LAYOUT JUMPER POSITIONING FIGURE A 1 Exploded View Board Layout...
Page 42: ...38 FIGURE A 2 CPU PWA...
Page 43: ...39 FIGURE A 3 OPTION PWA DC OUTPUT 2 OUTPUT 3...
Page 44: ...40...
Page 48: ...44...
Page 54: ...50...