APPLICATION

The Eagle 2000 Digital Communication Unit (DCU)
offers a convenient and economical means of obtain-
ing addressable gas detection.  The DCU digitizes a
4 to 20 ma analog signal from a sensor/transmitter
and transmits the value as a process variable to the
Eagle communication gateway.  All circuitry is housed
in a single explosion-proof/watertight enclosure for
location at the area of detection.

The DCU is provided in various configurations,
depending on the type of gas to be detected.  All
DCUs contain a communication module and a termi-
nal wiring board.  DCUs for detecting combustible
gas also contain a transmitter board.  

The Eagle DCU is available for use with Det-Tronics’
combustible gas, oxygen and toxic gas sensor/trans-
mitters.  The DCU can also be used with a wide vari-
ety of “third party” 4 to 20 ma analog instruments.

FEATURES

• Field addressable

• Unique patented fault isolation

• Utilizes state-of-the-art communication technology

• Pass through communication circuitry on power loss

• Ten bit signal resolution capability

• Two alarm setpoints

• Non-volatile memory for logging of alarm and cali-

bration events

• Non-intrusive one person calibration

• LED for calibration, fault and alarm status annuncia-

tion

• EMI hardened

• Screw terminal connectors.

SPECIFICATIONS

INPUT VOLTAGE—

24 vdc.  Operating range is 18 to 32 vdc.

INPUTS—

4 to 20 ma analog signal, with an input impedance of
200 ohms, 10 bit resolution.

OUTPUTS—

Digital communication, transformer isolated (78.5
kbaud).  Calibrated 0 to 4095 digital corresponds to 0
to full scale.

POWER CONSUMPTION—
DCU with toxic gas sensor/transmitter:

95 ma maximum.

DCU with transmitter and combustible gas sensor:

180 ma maximum during normal operation, 500 ma
during startup.

TEMPERATURE RANGE—

Operating:

–40°F to +167°F  (–40°C to +75°C).

Storage:

–67°F to +185°F  (–55°C to +85°C).

SPECIFICATION DATA

Eagle Quantum

Digital Communication Unit

EQ2200DCU

©

Detector Electronics Corporation 2001

10/01

90-1118-01

DET

-

TRONICS

®

Summary of Contents for Eagle Quantum EQ2200DCU

Page 1: ...patented fault isolation Utilizes state of the art communication technology Pass through communication circuitry on power loss Ten bit signal resolution capability Two alarm setpoints Non volatile mem...

Page 2: ...tus indicat ing LEDs that are visible through a viewing window on the enclosure cover and supports single person non intrusive calibration with a Det Tronics gas sensor DETECTOR ENCLOSURE The NEMA 4X...

Page 3: ...ork segment The DCU communicates with the LCU over the digital highway as shown in Figure 2 In the event of a single open or short circuit on the digital highway all units will be fully functional con...

Page 4: ...e Do not over tighten If a sensor separation kit is used attach the sensor to the separation kit junction box and wire the device as described in the Sensor Separation section CAUTION The sensor threa...

Page 5: ...ions for the detectors Whenever practical detectors should be placed where they are easily accessible for calibration WARNING Do not apply power to the system with the cover removed unless the area ha...

Page 6: ...ch other using the standoffs provided See Figure 8 NOTE Be sure to note correct orientation of the trans mitter board If the transmitter board is rotated 180 from proper orientation the device will no...

Page 7: ...sensor separation junction box This assembly can be separated from the DCUEX by up to 1000 feet using three conductor 18 AWG shielded cable Regardless of separation distance operating volt age at the...

Page 8: ...E mail detronics detronics com The specifications contained within this document are subject to change without notice R E GISTERED BY UL AND B S I N O A2305 NO 2582 6 ISO 9001 R E G I STERED F I R M R...

Reviews: