49
95-8714
6.3
CONNECTIONS AND HARDWARE
The HART Communicator can interface with the LS2000 from the control room or from any wiring
termination point in the analog output signal loop. To communicate, connect the HART communicator
in parallel with the LS2000 analog signal or load resistor. The connections are non-polarized. Refer to
the “Wiring Procedure” section for installation instructions.
NOTE
The HART Communicator needs a minimum of 250 ohms resistance in the loop to function
properly. The HART Communicator does not measure loop current directly.
ONLINE MENU
When HART communication is established with the receiver, the first menu displayed is the LS2000
Online menu:
To select any of the menu options shown, highlight the desired option using the up/down arrow key,
and then press the “right arrow” key.
COMMONLY USED HART COMMANDS
The most commonly used HART commands for the LS2000 are:
1. Setting the real time clock
2. Setting alarm thresholds and latch/nonlatch functions
3. Setting the analog fault code menu
4. Performing full system alignment
5. Performing zero calibration
6. Assigning a nonvolatile tag name to the receiver
7. Defining a nonvolatile descriptor for future reference
8. Interrogating the history menu for information including total running hours, max/min temperature,
calibration and event logs.
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
LS2000 RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Status Menu
1) General Info Menu
2) Device Info Menu
3) Sensor Info Menu
4) Fault Status Menu
5) History Menu
Device Info Menu
1) Universal Rev.
2) Field Device Rev.
3) Software Rev.
4) Write Protect
5) RTC Menu
6) Alignment Status Menu
RTC Menu
1) Seconds
2) Minutes
3) Hours
4) Date
5) Month
6) Day
7) Year
8) Write Protect
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Setup Menu
1) OPGD Option Menu
2) HART Output Menu
3) Com - 485 Menu
4) Config Flt Output Menu
5) Gas Type Menu
6) Range Menu
7) Alarm Menu
8) D/A Trim Method
9) RTC Menu
Alarm Menu
1) High Alarm Level
2) High Alarm Latch
3) Low Alarm Level
4) Low Alarm Latch
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Diag / Test Menu
1) Self Test
2) Response Test
3) Reset
4) Loop Test
5) Debug Menu
6) Alignment Menu
Alignment Menu
1) Quad X
2) Quad Y
3) Reference
4) Enable Alignment
5) Disable Alignment
OPGD RX Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
Online
1) Process Variables
2) Device Diagnostics
3) Configure/Setup
Calibration Menu
1) Gas Type
2) Cal Date
3) User Span Cal Delta
4) Zero Calibration Method