background image

OPERATING MODES

The OPECL has four operating modes: warm-up,
normal, alignment and calibrate. 

Warm-up

Warm-up mode is entered upon application of 24 Vdc
operating power.  During warm-up, the 4-20 mA current
loop output will indicate warm-up, the indicating LED is
amber, and the alarm outputs are disabled.  The warm-
up mode lasts nominally two minutes after power-up.

Normal

After warm-up mode is completed, the device
automatically enters the Normal mode, and all analog
and alarm outputs are enabled.

Alignment

The OPECL modules must be properly aligned before
normal operation is attained.  There are two alignment
procedures:

1. Basic Alignment requires the OPECL Alignment Kit.

2. Fine Alignment requires the OPECL Alignment Kit

and a handheld HART Communicator.

Calibrate

After alignment is completed, zero calibration is
required.  Span calibration of the OPECL is normally not
required; however, the user has the option to verify
proper calibration or to perform calibration procedures if
necessary.  Refer to the "Calibration" section in this
manual for details.

4 TO 20 MA CURRENT LOOP OUTPUT

OPECL provides a linear current loop output that is
proportional to the detected gas level.  Fault and
calibration status are also indicated by this output.

The factory default for full-scale 5 LFL-meters output is
20 mA.  MODBUS interfaces also have the ability to
calibrate the 4 mA and 20 mA levels.

FAULT INDICATION

Faults and status conditions are indicated using the 4-
20 mA analog signal output.  Refer to Table 3.
Signaling modes include two predefined and one user
defined mode.  PIR9400 mode (default) provides
compatibility with the DEC R8471J Gas Controller.
OPGD-Rx mode is available as well as a user defined
mode for third party compatibility.

5

95-8556

2.1

Default

Configurable Options

Gas Type

Methane

Methane, Ethane,

Propane, Butane, 

Propylene, Special

Measurement Range

0-5

0-2, 0-5

(LFL-M)

Low Alarm Threshold

1

0.25 to 3

(LFL-M)

High Alarm Threshold

2

1 to 3

(LFL-M)

Beam Block Delay

60 Seconds

3600 Seconds

Fault Mode

PIR9400

OPGD-Rx, User Defined

Table 2—Factory Default Settings

Status 4-20 

mA 

Level (±0.1)

PIR9400

OPGD-Rx

Normal Gas:  –0.5 to 5 LFL-M

2.4 to 20.0 

20.0

Warmup - Standard range model

1.0

1.0

Warmup - Long range model

1.0

1.0

Zero Calibration

2.2

1.0

Calibration Fault

1.6

1.0

Beam Block

1.0

2.0

Back-up Lamp Active*

2.4

3.0

Calibrate Active at Startup

0.6

1.0

EE Error

1.2

1.0

Ref. ADC Saturated

0.2

1.0

Active ADC Saturated

0.4

1.0

24 VDC Fault

0.8

1.0

Zero Drift

2.4

1.0

Flash CRC Error

1.2

1.0

RAM Error

1.2

1.0

Over Range

20.4

20.4

Table 3—Detector Status Conditions Indicated by Current Level

*Device is still functional.  Gas overrides this indication.

Summary of Contents for Open Path Eclipse OPECL

Page 1: ...Infrared Hydrocarbon Gas Detector Open Path Eclipse Model OPECL Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 87...

Page 2: ...1 Wiring Cable Requirements 11 Power Wiring Size and Maximum Length 12 Optional Relays 12 Wiring Procedure 13 STARTUP 16 ALIGNMENT 16 Overview 16 Basic Alignment Procedure 16 Fine Alignment Procedure...

Page 3: ...along with mounting fixture hardware Both modules are powered from an external 24 volt DC supply The receiver provides the measurement signal outputs and is furnished with an onboard status indicatio...

Page 4: ...ture A xenon lamp illuminates the linear detection path from the transmitter to the receiver In the event that the primary lamp fails the back up lamp is brought into service The receiver recognizes t...

Page 5: ...on via a flashing red color and a HIGH alarm condition via a steady red color The OPECL internal magnetic switch or HART Field Communicator can be used to reset latched alarms A short duration magneti...

Page 6: ...communicator for system setup commissioning and diagnostics Onboard LED Indicator Indicates normal fault and backup lamp operation status Green indicates normal operation Amber indicates operation in...

Page 7: ...this output The factory default for full scale 5 LFL meters output is 20 mA MODBUS interfaces also have the ability to calibrate the 4 mA and 20 mA levels FAULT INDICATION Faults and status conditions...

Page 8: ...or MODBUS communication FAULT RELAY Form C Type NO NC Energized during Normal mode De Energized on Fault or loss of power Contact Rating 5 amperes at 30 VDC Non Latching Operation only not programmab...

Page 9: ...001 see Appendix B Class I Div 2 Groups A B C D T4 Type 4X CENELEC Standard range and long range models 0539 II 2 G DEMKO 03 ATEX 135898X EEx de ib IIC T5 T5 Tamb 40 C to 60 C IP67 Transmitter Receive...

Page 10: ...diameter pipe Refer to Figure 3 for mounting dimensions SHIPPING WEIGHT Transmitter with mounting plate 35 pounds 16 kg Receiver with mounting plate 35 pounds 16 kg WARRANTY 3 year limited warranty f...

Page 11: ...por density and flashpoint should be identified and used to assist in selecting the optimum detector mounting locations within the area The detector must be installed by qualified personnel only follo...

Page 12: ...longterm outdoor operation in very cold climates is intended extra shielding covers are recommended to prevent accumulation of snow and ice on the windows Deluge and Flooding The modules are rated IP6...

Page 13: ...source of 24 Vdc power is being utilized verify that system requirements are met NOTE If disconnection of power is required separate disconnect capability must be provided WIRING CABLE REQUIREMENTS A...

Page 14: ...y the resistance of the wire ohms foot value available in wire manufacturer s specification data sheet 3 Divide by 2 For example Consider an installation using 18 AWG wiring with a power supply provid...

Page 15: ...g terminal configuration for the OPECL receiver with relays Figures 11 through 14 show the 4 to 20 mA output of the OPECL receiver in various wiring schemes Figure 15 shows the OPECL wired to a Model...

Page 16: ...N 4 to 20 MA B2051 TOTAL LOOP RESISTANCE 250 OHMS MINIMUM 600 OHMS MAXIMUM Figure 12 Detector Wired for Non Isolated 4 to 20 ma Current Output Sourcing Figure 11 Detector Wired for Non Isolated 4 to 2...

Page 17: ...Sinking CURRENT OUTPUT CHASSIS GROUND POWER SENSOR EXTERNAL RESET HIGH ALARM HIGH ALARM OC AUX ALARM AUX ALARM OC LOW ALARM LOW ALARM OC FAULT FAULT OC 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 TO 32 VD...

Page 18: ...g all OPECL systems The following instructions cover the use of the Telescope Alignment Tool 3 Calibration Magnet 4 For installations with module separation distances between 5 and 30 meters a range r...

Page 19: ...e to dead center on the window of the receiver module Tighten the vertical alignment locking nuts so that no movement will occur 17 95 8556 2 1 VERTICAL ALIGNMENT LOCKING NUTS 2 VERTICAL ADJUSTMENT BO...

Page 20: ...y performing a zero calibration 15 Perform a zero calibration Refer to Zero Calibration in the Calibration section of this manual Any faults or alarms that may be present as a result of the alignment...

Page 21: ...eceiver module s onboard HART communication port 2 Turn on the HART communicator and check for OPECL device recognition When HART communication is established the OPGD Rx Root menu will be displayed o...

Page 22: ...bject such as cardboard until a beam block fault is generated CALIBRATION CALIBRATION OVERVIEW Although routine calibration of the Open Path Eclipse is normally not required the device supports non in...

Page 23: ...Zero Calibration 1 Apply magnet for 2 seconds minimum to initiate calibration A The onboard LED turns to steady red B The current output decreases to 1 mA 2 When zero calibration is complete A The onb...

Page 24: ...ipment transportation prepaid to the factory in Minneapolis 22 95 8556 2 1 Fault Condition Corrective Action Low 24 volts 24 vdc operating voltage is out of range Verify proper wiring to the detector...

Page 25: ...t flange internal 009186 001 Spare Pan Tilt Mounting Kit for one OPECL module only 007907 001 Sun Shield for one module 008925 001 Spare electronics lamp module for OPECL transmitter 008926 001 Spare...

Page 26: ...priate DDL s for the Open Path Eclipse are included within your Communicator To review the device descriptions programmed into your HART Communicator 1 From the Main menu press to access Offline menu...

Page 27: ...igh Alarm Level 2 High Alarm Latch 3 Low Alarm Level 4 Low Alarm Latch RTC Menu 1 RTC Menu Setup Menu 1 OPGD Option Menu 2 Hart Output Menu 3 Com 485 Menu 4 Config Flt Output Menu 5 Gas Type Menu 6 Ra...

Page 28: ...first menu displayed is the OPGD RX Root menu To select any of the 5 menu options shown highlight the desired option using the up down arrow key and then press the right arrow key COMMONLY USED HART...

Page 29: ...RITTEN UNLESS OTHERWISE SPECIFIED DIMENSION TOLERANCE INCH MM INCH MM REMOVE ALL BURRS BREAK ALL EDGES AND SHARP CORNERS THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY INFORMATION AND ANY REPRODUC...

Page 30: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Reviews: