background image

NOTE

When power is applied to the controller, it enters
a time delay mode to allow the sensor output to
stabilize before beginning normal operation.
During this time the outputs are inhibited, the
FAULT LED is illuminated, and the current output
indicates a fault condition.  This time delay can
last up to five minutes, but will end earlier if the
sensor output no longer exceeds any alarm set-
points.

5.

If a sensor separation kit and K Series
Transmitters are being used, adjust the sensor
voltage to 3.3 vdc, following the procedure
described in the “Sensor Separation” section.

6.

If desired, controller operation can be tested by
manipulating the transmitter output to a level that
exceeds the alarm thresholds.  With K Series
Transmitters, this is done by adjusting the Zero
potentiometer.  [The transmitter Span adjustment
may have to be increased (clockwise) to obtain a
full scale reading on the controller.]  The output of
Model 400/405 Transmitters can be adjusted over
the entire operating range of the transmitter using
the optical calibration meter.  Refer to the trans-
mitter manual for details.  Note that this test will
actuate the controller outputs.

7.

Put the controller in the Setpoint Display mode to
determine the present alarm setpoints and cali-
bration gas concentration.  If changes are
required, perform the Setpoint Adjustment proce-
dure.

8.

Perform the calibration procedure.

9.

Check the 4 to 20 ma current loop for proper cali-
bration and adjust as required.

10. Remove mechanical blocking devices (if used)

and restore power to the output loads.

SETPOINT ADJUSTMENT

The adjustment range for the alarm setpoints and cali-
bration gas concentration is as follows:

Low alarm

5 to 40% LFL

High alarm

10 to 60% LFL

Auxiliary alarm

5 to 99% LFL

Calibration gas

30 to 99% LFL

The factory settings are:

Low alarm

20% LFL

High alarm

50% LFL

Auxiliary alarm

50% LFL

Calibration gas

50% LFL

To 

check

the present levels, use the “Setpoint Display

Mode” described below.  To 

change

the values, use

the “Setpoint Adjustment Procedure”.

SETPOINT DISPLAY MODE

1.

To enter the Setpoint Display mode, press and
hold the Reset button until the Low LED begins to
blink (approximately one second).  Release the
Reset button.  The low alarm setpoint will be
shown for two seconds on the digital display.

NOTE

The Reset button should be released as soon as
the controller has entered the Setpoint Display
mode (after one second).  If the button is still
depressed at the end of the Setpoint Display
mode (9 seconds), the controller will automatical-
ly enter the Calibrate mode.  If the operator is not
prepared to perform a calibration, a calibration
fault will occur.  Recycle power to the controller
to exit the calibrate mode without affecting the
calibration settings.

2.

At the end of the two second interval, the Low
LED goes out, the High LED begins to blink, and
the digital display shows the high alarm setpoint.

3.

Two seconds later the High LED goes out and the
Auxiliary LED blinks.  The digital display now
shows the programmed auxiliary alarm setpoint.

4.

Two seconds later the Auxiliary LED goes out and
the CAL LED blinks.  The digital display now
shows the programmed calibration gas concen-
tration.

5.

After displaying the calibration gas concentration
for two seconds, the controller automatically
leaves the Setpoint Display mode and returns to
the Normal operating mode.

6.

If adjustments to the setpoints are required, per-
form the Setpoint Adjustment procedure.  When
the setpoint levels are acceptable, record this
information for future reference and perform the
Calibration procedure.

SETPOINT ADJUSTMENT PROCEDURE

1.

Determine the required alarm setpoint levels and
calibration gas concentration.  If the system will
be used to detect a gas other than the type being
used for calibration, a conversion (“K”) factor

must

be used to determine the correct value to

be programmed into the microprocessor in step 5
below.  Refer to the “Calibration “ section.

17

95-8398

Summary of Contents for R8471A

Page 1: ...Instructions 95 8398 02 Combustible Gas Controller R8471A Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 612 941 5665 or 800 765 3473 Fax 612 829 8750 2 95...

Page 2: ...E 23 Manual Check of Output Devices 23 Checkout in Normal Mode 23 Sensor Replacement 23 Controller Calibration 24 Transmitter Calibration 24 TROUBLESHOOTING 24 LOSS OF SENSOR SENSITIVITY 24 REPLACEMEN...

Page 3: ...atible with Det Tronics R7400 series flame controllers Variety of racks available in 4U or 3U height config uration SPECIFICATIONS CONTROLLER OPERATING VOLTAGE 24 vdc Can operate in the range of 18 to...

Page 4: ...regarding use of the sensor in oxy gen deficient atmospheres HUMIDITY RANGE 0 to 99 RH non condensing HUMIDITY EFFECT Less than 5 percent full scale deviation at 10 to 90 RH SYSTEM APPROVAL The R8471A...

Page 5: ...formation section for more informa tion CONTROLLER Faceplate Description The faceplate of the controller provides LEDs for iden tifying status conditions a digital display and bar graph display for in...

Page 6: ...l is furnished with a set of four relays in place of the four solid state outputs The relays have SPST contacts rated 5 amperes at 30 vdc or 250 vac This model also includes a selectable isolated non...

Page 7: ...is on and indicates the sensor input in LFL Bar graph display reads the same as the digital display All LEDs are off Alarm outputs are in their normal state energized or de energized as programmed DC...

Page 8: ...by pressing the Reset button located on the front panel of the controller See Figure 3 When the Reset but ton is momentarily depressed all LEDs turn off and all outputs return to their normal conditio...

Page 9: ...ibration informa tion is lost Sensor calibration must be per formed even if the sensor was not replaced To enter the Sensor Replacement mode first enter the Calibrate mode as described above then pres...

Page 10: ...G REQUlREMENTS NOTE The wiring procedures in this manual are intend ed to ensure proper functioning of the device under normal conditions However because of the many variations in wiring codes and reg...

Page 11: ...ances and wire gauge will be different in each case Refer to the transmitter manual for information specific to that model Kit Description The sensor separation kit consists of the following Junction...

Page 12: ...onnected to earth ground at the transmitter junction box The shield of the cable connecting the transmitter and controller should be open at the transmitter junction box and connected to earth ground...

Page 13: ...n de classified 2 Remove the cover from the transmitter junction box NOTE The transmitter and controller contain semicon ductor devices that are susceptible to damage by electrostatic discharge An ele...

Page 14: ...BLK Power supply negative RED CTR Signal WHT Power supply positive 7 Check all field wiring to ensure that the proper connections have been made then pour the con duit seals and allow them to dry if...

Page 15: ...N LINE WITH THE CLIP IN THE BOTTOM BRACKET 3 GAS CONTROLLERS ARE APPROX ONE INCH WIDE AND REQUIRE ONE RAIL FOR INSERTION PLACE CLIPS IN LINE WITH GUIDE RAILS CAGES WILL ACCEPT AS MANY GAS CONTROLLERS...

Page 16: ...s 15 and 16 Fault Output 14 Figure 10 A Typical System with Relay Outputs and Non Isolated Current Output CURRENT OUTPUT CHASSIS GROUND POWER SENSOR EXTERNAL RESET HIGH ALARM HIGH ALARM OC AUX ALARM A...

Page 17: ...uctive load with a diode used for transient suppression CONTROLLER PROGRAMMING Refer to Figure 13 to determine the location of pro gramming jumpers and switches Table 1 shows the selectable options fo...

Page 18: ...uble checking the system to be sure that all phases of system installation are complete and have been performed correctly 1 Sensors are pointing down and junction boxes are securely mounted 2 Optional...

Page 19: ...ation gas 50 LFL To check the present levels use the Setpoint Display Mode described below To change the values use the Setpoint Adjustment Procedure SETPOINT DISPLAY MODE 1 To enter the Setpoint Disp...

Page 20: ...bility The sensor must be calibrated Before a new system is initially put into service If the sensor is replaced If the transmitter is replaced If the controller is replaced If the sensor is exposed t...

Page 21: ...s requires removing the enclosure cover therefore the hazardous area must be de classified When transmitter calibration is performed an ini tial calibration of the controller must be completed in addi...

Page 22: ...to ensure that the area is clear of any combustible gases If there is any indication of the presence of com bustible gas at the sensor calibration or mainte nance should not be performed The location...

Page 23: ...d holding the RESET button on the controller faceplate for approximately 9 seconds until the digital display begins flashing and the CAL LED is illuminated Release the RESET button 3 Press the SET but...

Page 24: ...pro cedure is not recommended 3 Depress and hold the Reset button until the CAL LED is illuminated and the digital display starts to flash approximately 9 seconds 4 When the Zero calculations are com...

Page 25: ...CHECK OF OUTPUT DEVICES Fault detection circuitry continuously monitors for an open sensing element excessive negative zero drift open sensor wiring and various other problems that could prevent prope...

Page 26: ...com bustible gas sensors Interfering or contaminating substances that can adversely affect the response of the sensor to combustible gases are as follows A Materials that can clog the pores of the si...

Page 27: ...button If RESET is pressed recalibrate and check setpoints F96 Status 1 Input power problem should be18 to 32 volts Check operation of power source and power wiring F97 Status 1 Controller type inval...

Page 28: ...re removing the device from the mounting cage or plugging in the replacement unit The sensing element is mounted in a sealed housing and is not intended to be repaired When calibration can no longer b...

Page 29: ...ngineers Pvt Ltd Veers Desai Road Andheri West Bombay 400 053 INDIA Telephone 91 22 632 2374 Facsimile 91 22 632 2374 Dial Detector Electronics Southern Europe Ciodue FSI Via Stephenson 43 A 20157 Mil...

Page 30: ...nal relay contacts SENSORS Specify standard poison resistant or high tempera ture sensor in aluminum or stainless steel housing SENSOR SEPARATION KITS Specify whether used with K Series Model 400 405...

Page 31: ...29...

Page 32: ...Recommended Test Form Detector Detector Date Date Date Number Location Installed Checked Calibrated Remarks 30...

Page 33: ...95 8398 Fault Record Sheet Date Time Detector System Status Operator Comments Affected 31...

Page 34: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 612 941 5665 or 800 765 3473 Fax 612 829 8750...

Reviews: