Page 30 P/N 39818D Copyright © 2001 Detection Systems, Inc. DS7080iP-32 Reference Guide
9.17 Address 017 - 022 - Phone Numbers
Address 017-018 Phone # 1 (Reporting)
Address 019-020 Phone # 2 (Reporting)
Address 021-022 Phone # 3 (Remote Programmer)
Address 017 Phone # 1 (digits 1-16):
___________________________________________
Address 018 Phone # 1 (digits 17-32):
___________________________________________
Address 019 Phone # 2 (digits 1-16):
___________________________________________
Address 020 Phone # 2 (digits 17-32):
___________________________________________
Address 021 Phone # 3 (digits 1-16):
___________________________________________
Address 022 Phone # 3 (digits 17-32):
___________________________________________
To dial the [*] character, enter *1 (The [*] character is sent as “1” “1” when pulse dialing). The Letter “B” will be displayed.
To dial the [#] character, enter *2 (The [#] character is only valid when tone dialing). The letter “C” will be displayed.
To input a 3 second delay, enter *3. The letter “D” will be displayed.
To wait for the dial tone, enter *4 as the first digit of the phone number. The letter “E” will be displayed (only if it is programmed as
the first digit).
To disable a phone number, enter *5 as the first digit. The underscore “_” will be displayed
To delete the phone number from the display window, enter *5 in all the digits.
9.18 Address 023 - Dial Attempts
Dial Attempts determines the maximum number of times the control panel will attempt to contact the central station on each programmed
phone number before a Comm. Fail is alerted.
After all dial attempts are made, the panel will log a communications failure. It will then wait 30 minutes and attempt to dial again
repeating the programmed number of attempts. If it still fails to connect the panel will then wait 24 hours and make another
attempt. It will continue to attempt to dial once every 24 hours after that until it is successful.
Example: If Address 023 is programmed for 003 (3 dial attempts), the panel will try 3 times to connect. If all 3 attempts fail, the
panel will log the communications failure, wait 30 minutes and try again making 3 more attempts to dial. If the second round of
3 attempts fails, the panel will wait 24 hours and try again making another 3 attempts to dial. It will continue trying to connect
every 24 hours afterward making 3 attempts each time.
PSTN Warning Notice: Under certain adverse conditions on the Public Switched Telephone Network (PSTN), some control/
communicators may require more than two dial attempts to reach the central station receiver. To guard against such a situation,
it is recommended that the Dial Attempts be set to a value between 3 and 10.
9.19 Address 024 - Auto Test / Remote Programmer Call-Out Day