Page 32 P/N 39818D Copyright © 2001 Detection Systems, Inc. DS7080iP-32 Reference Guide
9.24 Addess 029 - Keypad Reports
Keypad Reports are programmed for the value you wish to send to the central station when the emergency keys are pressed.
DEFAULT
00 00 00 00
KEYPAD FIRE REPORT
KEYPAD FIRE RESTORAL REPORT
KEYPAD EMERGENCY ALARM REPORT
KEYPAD PANIC ALARM REPORT
00
KEYPAD TAMPER REPORT
00
KEYPAD TAMPER RESTORAL REPORT
Two Digits, 00 through FF
9.25 Address 030, 031, 032, 033 - Zone Type
• Disabled: These zones are not monitored, and will not generate alarm or trouble conditions.
• Perimeter Instant: These zones arm and disarm with the panel, and never have entry or exit delays. Violation of this type of zone will
cause an intrusion alarm.
• 24-Hour: This is a zone programmed to activate when its loop is faulted, even if the system is disarmed. An alarm on a 24-hour zone
(fire or intrusion) will be silenced by entering a disarm code whether the control is armed or not. If the 24-hour zone restores and alarms
again the alarm will sound again. 24-hour zones may generate trouble conditions during armed or disarmed periods. All 24-hour zones
that have alarmed and are not restored will show as “Not Ready.” They will prevent arming unless the panel is force armed. 24-hour
zones that have been bypassed manually will remain so until manually unbypassed, even if the control is armed and disarmed. Bypasses
of these zones will be displayed on the keypad.