DS7080iP-32 Reference Guide Copyright © 2001 Detection Systems, Inc. P/N 39818D Page 43
10.2.1
Special Requirements for Partitioned Systems
• The control unit and burglar alarm signal are intended to be
installed in one premesis, under one management, one ownership
and one address which is then partitioned.
• The indicating device (bell) must be placed where it can be heard
by all partitions.
• The local commercial burglar alarm indicating device must be
installed in an area where the Audible Test can be heard by any
of the users in the different partitions.
• The commercial local control unit should be protected by either
being lined and connected to a 24 hour burglar alarm circuit or
they shall be in a protected area which is armed 24 hours a day.
In either case the zone which is protecting the control unit and
power supply must be programmed not to be bypassed.
• Remote programming must not be used to disarm the system.
10.3 Programming the DS7080iP-32
When used for UL Listed Requirements, the control must conform
to certain programming requirements. The following is a list of the
required program entries and required accessories for specific UL
Listed Requirements.
10.3.1 Household Fire Alarm
Household Fire Alarm using Digital Alarm Communicator Transmitter
with local bell. The control must be installed in accordance with
NFPA 72.
Required Accessories:
• At least one Detection Systems’ model DS250 Series smoke
detector with an MB Series base, or another Listed compatible
smoke detector.
• At least one DS7480 Bell Supervision Module.
• One Wheelock 46T-G10-12 bell or 34T-12 horn (will provide 85dB
for UL985 and NFPA 72 requirements; other Listed compatible
devices with a voltage range of 11.8 to 12.4 V nominal or better
may be used) is required for this application and must be installed
inside the protected area.
• The standard control enclosure can be used.
• At least one DS7447 or DS7445 Keypad must be used.
• Four-wire detectors must be used with Listed power supervision
devices. A compatible Listed 4-wire detector is the Detection
Systems, Inc. DS250 in an MB4W base. A compatible Listed EOL
relay is the Detection Systems, Inc. EOL200.
• All zones must be used with the EOL resistor (P/N 25899),
provided.
A. Report Programming:
•
Fire Zone Report must be programmed.
•
Low Battery Report (Program Address 079, digits 1 & 2) must
be programmed.
•
AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
B. Timer Programming:
•
Bell Cutoff Times (Program Address 010, digits 10-15) must be
programmed for not less than 4 minutes.
C. Zone Programming:
•
Fire zones must be programmed for alarm on short, trouble on
open, not be cross-zoned or be part of custom arming.
D. Alarm Output Programming:
•
Alar m Output (Program Address 009 digit 1) must be
programmed as *0 (A).
E. General Control Programming:
•
Program Address 002 must be programmed as: Digits 8 & 9 = 0
(do not allow force arming).
10.3.2 Grade A Household Burglary Alarm
Grade A Household Burglar y Alar m using Digital Alarm
Communicator Transmitter with local bell. The control must be
installed in accordance with UL Standard UL1641.
Required Accessories:
• At least one Wheelock 46T-G10-12 bell or 34T-12 horn (other
Listed compatible devices with a voltage range of 11.8 to 12.4 V
nominal or better may be used) is required for this application.
• The standard DS7080iP-32 enclosure can be used.
A. Report Programming:
• Burglar Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 079, digits 1 & 2) must be
programmed.
• AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
B. Timer Programming:
• Bell Cutoff Times (Program Address 010, digits 10-15) must be
programmed for not less than 4 minutes.
• Entry Delay Timers (Program Address 010, digits 1-6) must be
programmed for not longer than 60 seconds.
• Exit Delay Timer (Program Address 010, digits 7-9) must be
programmed for not longer than 45 seconds.
C. General Control Programming:
• Program Address 002, digit 3, must be programmed for no swinger
shunts (enter 0).
• Program Address 002, Force Arming Limit, must be programmed
as: digits 8 & 9 = 0.
• Cross zoning time programming (Program Address 006) must be
set to 000.
• Program Address 008, digit 2, must be programmed for the
Commercial mode (digit 2 = 0).
D. Alarm Output Programming:
• Alarm Output, Program Address 009, digit 1 must be programmed
as *0 (A).
10.3.3 Local Burglary Alarm
The control must be installed in accordance with UL Standards
UL681 and UL609 for all grades of service.
A. Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Required Accessories:
• The control must be installed in a Detection Systems’ model
AE7080CC enclosure with a cover actuated tamper switch
installed.
• The Ademco Model AB-12 bell/housing (see Section 10.4).
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 079, digits 1 & 2) must be
programmed.