DS7080iP-32 Reference Guide Copyright © 2001 Detection Systems, Inc. P/N 39818D Page 45
10.3.5 Central Station Burglary Alarm
The control must be installed in accordance with UL Standards
UL611 and UL681 for all grades of service.
A. Grades AA and A Installations using the Applied Spectrum
PAL200 and the DACT
Required Accessories:
• The control must be installed in a Detection Systems’ model
AE7080CC enclosure with a cover actuated tamper switch
installed.
• The Applied Spectrum PAL200.
• The Spectrum PAL200 must be installed within 3 feet of the control
and the wiring to the control must be in conduit.
• The Applied Spectrum PAL200 inputs should be connected to
the alarm outputs (the active alarm sounder output may be used).
1. Report Programming:
• Programming shall be enabled to allow all alarm signals to be
transmitted via the DACT and PAL200.
• Burglar Zone Reports are not required since the alarms are
transmitted over the PAL200.
• Low Battery Report (Program Address 079, digits 1 & 2) must be
programmed.
• AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
• Open Report (Program Addresses 011, digit 1, and 078, digits 1
& 2) must be programmed.
• Close Report (Program Addresses 011, digit 1, and 078, digits 3
& 4) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 082, digits 1-4,
024 and 025, all digits) must be programmed.
2. Timer Programming:
• Entry, Exit Delay Times (Program Address 010, digits 1-9) must
be programmed for not longer than 60 seconds.
3. General Control Programming:
• Program Address 002, digit 2, must be programmed for Closing
Ringback and digit 3 must be programmed for no swinger shunts.
• Program Address 002, Force Arming Limit, must be programmed
as: digits 8 & 9 = 0.
• Program Address 008, digit 2, must be programmed for the
Commercial mode (digit 2 = 0).
4. Zone Programming:
• The Burglar alarm output signal (whether pulsed or steady) must
be different from the Fire alarm signal.
5. Alarm Output Programming:
• Alarm Output, Program Address 009, digit 1 must be programmed
as *0 (A).
B. Grade B Installations using Digital Alarm Communicator
Transmitter with local bell
Required Accessories:
• The control must be installed in a Detection Systems’ model
AE7080CC enclosure with a cover actuated tamper switch
installed.
• The Ademco Model AB-12 bell/housing (see Section 10.4).
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 079, digits 1 & 2) must be
programmed.
• AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
• Open Report (Program Addresses 011, digit 1, and 078, digits 1
& 2) must be programmed.
• Close Report (Program Addresses 011, digit 1, and 078, digits 3
& 4) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 082, digits 1-4,
024 and 025, all digits) must be programmed.
2. Timer Programming:
• Bell Cutoff Times (Program Address 010, digits 10-15) must be
programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Address 010, digits 1-9) must
be programmed for not longer than 60 seconds.
3. General Control Programming:
• Program Address 002, digit 2, must be programmed for Closing
Ringback and digit 3 must be programmed for no swinger shunts.
• Program Address 002, Force Arming Limit, must be programmed
as: digits 8 & 9 = 0.
• Program Address 008, digit 2, must be programmed for the
Commercial mode (digit 2 = 0).
4. Zone Programming:
• The Burglar alarm output signal (whether pulsed or steady) must
be different from the Fire alarm signal.
5. Alarm Output Programming:
• Alarm Output, Program Address 009, digit 1 must be programmed
as *0 (A).
C. Grade C Installations using Digital Alarm Communicator
Transmitter only
Required Accessories:
• The control must be installed in a Detection Systems’ model
AE7080CC enclosure with a cover actuated tamper switch
installed.
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 079, digits 1 & 2) must be
programmed.
• AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
• Open Report (Program Addresses 011, digit 1, and 078, digits 1
& 2) must be programmed.
• Close Report (Program Addresses 011, digit 1, and 078, digits 3
& 4) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 082, digits 1-4,
024 and 025, all digits) must be programmed.
2. Timer Programming:
• Entry, Exit Delay Times (Program Address 010, digits 1-9) must
be programmed for not longer than 60 seconds.
3. General Control Programming:
• Program Address 002, digit 2, must be programmed for Closing
Ringback and digit 3 must be programmed for no swinger shunts.
• Program Address 002, Force Arming Limit, must be programmed
as: digits 8 & 9 = 0.