Page 50 P/N 39818D Copyright © 2001 Detection Systems, Inc. DS7080iP-32 Reference Guide
12.0
Report Programming Values Sent
12.1 SIA Format
SIA reporting allows the installer to select the type of event each report will send
to the central station. For example, if a burglary zone is used as a 24 hour panic
zone, it can now report as a PA (panic alarm) when using the SIA format.
The event type is programmed in the extended digit of the report (Addresses 054-
082 and 117-123). To activate a report when using the SIA format, place a “1” in
the first reporting digit. To select the type of event for this report, place one of the
following values in the second digit.
Data Digit 2 value SIA Report
Explanation
1
PA
Panic Alarm
2
PR
Panic Restore
3
QA
Emergency Alarm
4
QR
Emergency Restore
5
TA
Tamper Alarm
6
TR
Tamper Restore
7
UA
Untyped Zone Alarm
8
UR
Untyped Zone Restore
9
UT
Untyped Zone Trouble
*0
UJ
Untyped Trouble Restore
*1
YP
Power Supply Trouble
*2
YQ
Power Supply Restore
*3
YX
Service Required