Page 6 P/N 39818D Copyright © 2001 Detection Systems, Inc. DS7080iP-32 Reference Guide
3.0
Control Terminal Wiring
ZONES 1-8:
Zones 1-8 are for connection of NO or
NC alarm contacts. These zones require a 2.21K ohm
resistor (P/N 25899) at the end of the loop. Power is
momentarily removed after a [PIN] [System Reset]
during a fire verification. Only zone 1 may be used for
compatible 2-wire smoke detectors (up to 20). Zone
programming is done in address 034 for zones 1-8.
18
19
20
21
22
23
24
25
26
KEYPAD*:
Up to 4 keypads may be
used.
9
10
11
12
R
B
G
Y
Keypad(s)*
DS7488
Octal
Relay
13
14
15
16
17
TRBL
PO2
1
2
3
4
5
6
7
8
TRBL
:
Trouble Input. For
the connection of any
accessory that provides a dry
contact trouble output.
PO2:
PO2 supplies 12-12.5 v
and up to 500 mA when
activated. PO2 function
programmed in address 009.
*= Maximum Wire length each.
DS7443: 400 ft. (122m) maximum wire length.
Total in system: 1600 ft. (488M). Each keypad must be
a “home run”. Do not “daisy chain” keypads.
Trouble input is
non-supervised.
Do not use an
EOL resistor.
DS7488 Octal Relay
and EX8 Expansion
Modules. 1000 ft.
(305m) maximum
wire length. Must be
"Home Run". Do not
"Daisy Chain" with
keypads. The
DS7488 and EX-8
can only be “Home
Run.”
Shared cable is not
allowed for keypad
expansion modules,
telephone, or siren
wiring.
Do not use shielded
or twisted pair cable.
IMPORTANT
EX8
Expansion
Modules
DS7445/DS7447: 1000ft. (305m) maximum wire length.
Total in system: 4000ft. (1220m). Keypads may be
“home run” or “daisy chained”. Maximum of 2 keypads
per run for #22 AWG (.8mm) or 3 keypads for 18 AWG (1.0mm).
Option Bus
Quick Connect
TYPICAL BURGLAR AND FIRE WIRING
Typical 2-wire
smoke detector
wiring
(for a list of
compatible 2-wire
smoke detectors,
see Technical Service
Note P/N 41150)
EOL
Resistor
Smoke
Detector
Zone 1 Only
14
15
Typical 4-wire smoke
detector wiring.
For example:
Detection System's DS250
in an MB4W base.
EOL
Resistor
EOL Relay
Smoke
Detector
EOL
Resistor
EOL Relay
Smoke
Detector
Zone 1 Only
Zones 2-8 Only
14
14
15
16
Danger of explosion if battery
is incorrectly replaced.
Replace only with the same or
equivalent type recommended
by the manufacturer. Dispose of
used batteries according to the
manufacturer's instructions.
CAUTION
NO
Typical burglar
alarm loop wiring
Ground
Zone
Input
NC
CAUTION: Incorrect connections may
result in damage to the unit.
This System is Power Limited except for the
Battery terminals. All wiring entering this
enclosure must be Power Limited.
Before servicing this
equipment, remove all
power including the
transformer and battery.
Also remove the phone
line connection.
WARNING
CAUTION:
An appropriate two pole
disconnect device must be
installed by qualified service
personnel, as part of the
building installation.
AC INPUT :
Use a listed Class 2,16.5 VAC
40 VA transformer Model D1640
requires 60 Hz unswitched
dedicated outlet - do not share.
ALARM OUTPUT:
Provides 12 VDC, special
application, up to 1 A for powering bells, siren
drivers, etc. Function programmed in address
009.
1
2
3
4
5
6
7
8
AC
–
+
–
+
AC
AUX
PO1
PO1:
Shorts to Auxiliary (-) when activated. Can sink
up to 1 A. Programmed in Address 009.
EARTH GROUND:
Connected to a good earth
ground and to the cabinet cover.
AUXILIARY POWER:
Provides 12 VDC, special
application, up to 1 A for powering detectors.